Island Fallback Scenarios

Advanced Configuration Features

Island Fallback Scenarios

Introduction

In the event of a communications failure on the island or between the island and the

 

fieldbus, output data is put into a safe fallback state. In this state, output data is

 

replaced with pre-configured fallback values, ensuring that a module’s output data

 

values are known when the system recovers from a communications failure.

 

 

Fallback

There are several scenarios in which Advantys STB output modules go into their

Scenarios

fallback states:

 

loss of fieldbus communications—Communications with the PLC are lost.

 

loss of island bus communications—There is an internal island bus

 

communications error, indicated by a missing heartbeat message from either the

 

NIM or a module.

 

change of operating state—The NIM may command the island I/O modules to

 

￿switch from a running to a non-running (stopped or reset) state.

 

missing or failed mandatory module—The NIM detects the absence or failure of

 

a mandatory island module.

 

 

 

Note: If a mandatory (or any other) module fails, it needs to be replaced. The

 

module itself does not go into its fallback state.

 

 

 

In all of these fallback scenarios, the NIM disables the heartbeat message.

 

 

Heartbeat

The Advantys STB system relies on a heartbeat message to ensure the integrity and

Message

continuity of communications between the NIM and the island modules. The health

 

of island modules and the overall integrity of the Advantys STB system are

 

monitored through the transmission and reception of these periodic island bus

 

messages.

 

Because island I/O modules are configured to monitor the NIM’s heartbeat

 

message, output modules will go into their fallback states if they do not receive a

 

heartbeat message from the NIM within the defined interval.

 

 

890USE17700 April 2004

161