Modbus Error Codes

Data Exchange

Modbus Error Codes

Introduction

During operations, you may encounter Modbus error codes that are returned by the

 

STB NIP 2212 NIM to the Advantys configuration software. These error codes are

 

displayed as byte codes in hexadecimal format.

 

 

 

 

 

Note: Because the STB NIP 2212 NIM supports Modbus over a serial interface,

 

the Ethernet-based Modbus server does not support Modbus requests with a unit

 

ID of 255 (0xFF). In the PL7 programming tool, the default value for the field unit

 

ID when adding an I/O scanner connection is 255 (0xFF). Be aware that the NIM

 

drops packets with this unit ID.

 

General Error

 

 

 

 

 

 

 

 

 

Codes

 

 

 

Error Code

Error Type

Description

 

 

 

 

 

 

0x01

Illegal function

This error code is returned when the Advantys

 

 

 

configuration software attempts to modify the

 

 

 

configuration of the STB NIP 2212 when the software

 

 

 

does not have control.

 

 

 

 

 

0x03

Illegal Modbus

This error code may indicate any of the following

 

 

data value

conditions:

 

 

 

the function code contains incorrect data

 

 

 

a request is being issued while the NIM is in the

 

 

 

wrong operating mode—for example, COMM state

 

 

 

￿protected

 

 

 

you have entered the wrong password

 

 

 

 

 

 

 

 