Schneider Electric 890USE17700 manual Configuring a, Reflex Action, Inputs to a Reflex

Models: 890USE17700

1 194
Download 194 pages 47.07 Kb
Page 157
Image 157
Configuring a

 

 

 

 

 

 

 

 

 

 

 

 

 

Advanced Configuration Features

 

 

 

 

 

 

 

 

 

 

 

 

 

Configuring a

Each block in a reflex action must be configured using the Advantys configuration

Reflex Action

software.

 

 

 

 

 

 

 

 

 

 

 

Each block must be assigned a set of inputs and a result. Some blocks also require

 

that you specify one or more user-preset values—a compare block, for example,

 

requires that you preset threshold values and a delta value for hysteresis.

 

 

 

 

 

 

 

 

 

 

 

 

 

Inputs to a Reflex

The inputs to a reflex block include an enable input and one or more operational

Action

inputs.The inputs may be constants or they may come from other I/O modules on

 

the island, from virtual modules or outputs from another reflex block. For example,

 

an XOR block requires three inputs—the enable and two digital inputs that contain

 

the Boolean values to be XORed:

 

 

 

 

 

 

 

 

 

 

enable

 

 

 

 

 

XOR

 

 

 

 

operational input 1

 

 

 

 

 

 

 

 

 

 

 

result

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operational input 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Some blocks, such as the timers, require reset and/or trigger inputs to control the

 

reflex action. The following example shows a timer block with three inputs:

enable Reflex ActionInputs to a Reflex

trigger ActionManual background

reset Manual backgroundManual background

timer

time unit x terminal count

Manual backgroundManual background result

The trigger input starts the timer at 0 and accumulates time units of 1, 10, 100 or 1000 ms for a specified number of counts. The reset input causes the timer accumulator to be reset.

An input to a block may be a Boolean value, a word value, or a constant, depending on the type of reflex action it is performing. The enable input is either a Boolean or a constant always enabled value. The operational input to an block such as a digital latch must always be a Boolean, whereas the operational input to an analog latch must always be a 16-bit word.

You will need to configure a source for the block’s input values. An input value may come from an I/O module on the island or from the fieldbus master via a virtual module in the NIM.

Note: All inputs to a reflex block are sent on a change-of-state basis. After a change-of-state event has occurred, the system imposes a 10 ms delay before it accepts another change of state (input update). This feature is provided to minimize jitter in the system.

890USE17700 April 2004

157

Page 157
Image 157
Schneider Electric 890USE17700 manual Configuring a, Reflex Action, Inputs to a Reflex