Configuring the Island Bus

Initial

Use the following procedure to set up an island bus with configuration data that was

Configuration

previously saved (See Saving Configuration Data, p. 163) to a removable memory

and Reconfigu-

card. You can use this procedure to configure a new island or to overwrite an

ration Scenarios

existing configuration. Note: Using this procedure will destroy your existing

 

configuration data.

 

 

 

 

 

 

Step

Action

Result

 

 

 

 

 

1

Install (See Installing the

 

 

 

STB XMP 4440 Optional

 

 

 

Removable Memory Card,

 

 

 

p. 50) the removable

 

 

 

memory card in its drawer

 

 

 

in the NIM.

 

 

 

 

 

 

2

Power on the new island

The configuration data on the card is checked. If the

 

 

bus.

data is valid, it is written to Flash memory. The system

 

 

 

restarts automatically, and the island is configured with

 

 

 

this data. If the configuration data is invalid, it is not

 

 

 

used and the island bus will stop.

 

 

 

If the configuration data was unprotected, the island

 

 

 

bus remains in edit mode. If the configuration data on

 

 

 

the card was password-protected (See Protecting

 

 

 

Configuration Data, p. 164), your island bus enters

 

 

 

protected mode at the end of the configuration

 

 

 

process.

 

 

 

Note: If you are using this procedure to reconfigure an

 

 

 

island bus and your island is in protected mode, you

 

 

 

can use the configuration software to change the

 

 

 

island’s operational mode to edit.

 

 

 

 

 

 

 

 

Configuring

You can use a removable memory card to make a copy of your configuration data;

Multiple Island

then use the card to configure multiple island buses. This capability is particularly

Buses with the

advantageous in a distributed manufacturing environment or for an OEM (original

Same Data

equipment manufacturer).

 

Note: The island buses may be either new or previously configured, but the NIMs must all run the same fieldbus protocol.