Result of a Reflex Depending on the type of reflex block that you use, it will output either a Boolean or

Advanced Configuration Features

Result of a Reflex Depending on the type of reflex block that you use, it will output either a Boolean or

Blocka word as its result. Generally, the result is mapped to an action module, as shown in the following table:

Reflex Action

Result

Action Module Type

 

 

 

Boolean logic

Boolean value

digital output

 

 

 

integer compare

Boolean value

digital output

 

 

 

counter

16-bit word

first block in a nested reflex action

 

 

 

timer

Boolean value

digital output

 

 

 

digital latch

Boolean value

digital output

 

 

 

analog latch

16-bit word

analog output

 

 

 

The result from a block is usually mapped to an individual channel on an output module. Depending on the type of result that the block produces, this action module may be an analog channel or a digital channel.

When the result is mapped to a digital or analog output channel, that channel becomes dedicated to the reflex action and can no longer use data from the fieldbus master to update its field device.

The exception is when a reflex block is the first of two actions in a nested reflex action.

158

890USE17700 April 2004

Page 158