Schneider Electric 890USE17700 manual Fields on the Master Configurator Web Page

Models: 890USE17700

1 194
Download 194 pages 47.07 Kb
Page 80
Image 80
Fields on the Master Configurator Web Page

STB NIP 2212 Web Server

Fields on the Master Configurator Web Page

The fields on the Master Configurator web page are described in the following table:

Field

Legal Values

Description

 

 

 

Protocol

IP

The IP address (See How the STB NIP 2212 Obtains

 

 

IP Parameters, p. 60) of the master configurator on the

 

 

Ethernet LAN.

 

 

 

 

serial

The master configurator is attached to the CFG port on the

 

 

STB NIP 2212.

 

 

 

 

disabled

Disabled is the default setting for this feature.

 

 

If selected, the master configurator feature is disabled.

 

 

However, devices normally capable of configuring the island

 

 

will perform as designed.

 

 

 

reservation

0 ... 120000 ms,

The amount of time in ms allocated to a master for writing

time

with a 1 ms

configuration data to the STB NIP 2212. Other masters

 

resolution time

attempting to configure the island during this time will receive

 

 

an error message.

 

 

The default reservation time is 60,000 ms (1 min).

 

 

Reservation time is self-renewing.

 

 

 

Configuring a Master Configurator for the Island

Use the following procedure to configure a master configurator for an Advantys STB island:

Step

Action

 

 

1

Click on the Configuration tab to display the Configuration menu.

 

 

2

Select the Master Configurator option.

 

 

3

To￿identify the master configurator, do one of the following:

 

Click on the radio button next to the IP option and type in the IP address for

 

the master configurator communicating via the fieldbus (Ethernet) port (See

 

STB NIP 2212 Network Interface, p. 26), e.g., 139.158.2.38 (See Sample

 

Master Configurator Web Page, p. 81).

 

For a master configurator attached to the STB NIP 2212’s CFG port (See

 

￿The CFG Interface, p. 33), click on the radio button next to the Serial option.

 

To disable this feature, click on the radio button next to the Disabled (default)

 

option.

 

 

4

Type a value for the reservation time (0 ... 120000 ms). This is the amount of

 

time allocated to the master configurator for writing configuration data to the

 

island. The default setting is 60000 ms (1 min).

 

 

5

Click on the Save button to store the information about the master configurator

 

in the STB NIP 2212’s Flash memory and in RAM.

 

 

 

 

80

890USE17700 April 2004

Page 80
Image 80
Schneider Electric 890USE17700 Fields on the Master Configurator Web Page, The IP address See How the STB NIP 2212 Obtains