Standard

Introduction

Standard

You may also install one or more standard CANopen devices on an island. These

CANopen

devices are not auto-addressable, and they must be installed at the end of the island

Devices

bus. If you want to install standard CANopen devices on an island, you need to use

 

an STB XBE 2100 CANopen extension module as the last module in the last

 

segment.

Note: If you want to include standard CANopen devices in your island, you need to configure the island using the Advantys configuration software, and you need to configure the island to operate at 500 kbaud.

Because standard CANopen devices cannot be auto-addressed on the island bus, they must be addressed using physical addressing mechanisms on the devices. The standard CANopen devices together with the CANopen extension module form a sub -network on the island bus that needs to be separately terminated at the beginning and end. A terminator resistor is included in the STB XBE 2100 CANopen extension module for one end of the extension sub-network; the last device on the CANopen extension must also be terminated with 120 . The rest of the island bus needs to be terminated after the CANopen extension module with an

STB XMP 1100 termination plate:

1

5

6

7

9

 

 

 

 

23

CANopenDevices8 4

1primary segment

2NIM

3STB XBE 1000 EOS bus extension module

41 m length STB XCA 1002 bus extension cable

5extension segment

6STB XBE 2100 CANopen extension module

7STB XMP 1100 termination plate

8typical CANopen cable

7standard CANopen device with 120 termination

Length of the

The maximum length of an island bus—the maximum distance between the NIM and

Island Bus

the last device on the island—is 15 m (49.2 ft). This length must take into account

 

the extension cables between segments, extension cables between preferred

 

modules, and the space consumed by the devices themselves.

 

 