The STB NIP 2212 NIM

Calculating the The amount of power (See Logic Power Flow, p. 38) that the external power supply

Wattage must deliver is a function of the number of modules and the number of built-in power

Requirement supplies installed on the island.

The external supply needs to provide 13 W of power for the NIM and 13 W for each additional STB power supply (like an STB XBE 1200 BOS module). For example, a system with one NIM in the primary segment and one BOS module in an extension segment would require 26 W of power.

For example, the figure below shows an extended island:

124 VDC source power supply

2NIM

3PDM

4primary segment I/O modules

5BOS module

6first extension segment I/O modules

7second extension segment I/O modules

8island bus terminator plate