The CFG Interface

The STB NIP 2212 NIM

The CFG Interface

Purpose

The CFG port is the connection point to the island bus for either a computer running

 

the Advantys configuration software or an HMI panel.

 

 

Physical

The CFG interface is a front-accessible RS-232 interface located behind a hinged

Description

flap on the bottom front of the NIM:

The port uses a male eight-pin HE-13 connector.

Port Parameters The CFG port supports the set of communication parameters listed in the following table. If you want to apply any settings other than the factory default values, you must use the Advantys configuration software:

Parameter

Valid Values

Factory Default Settings

 

 

 

bit rate (baud)

2400 / 4800 / 9600 / 19200 /

9600

 

38400/ 57600

 

 

 

 

data bits

7/8

8

 

 

 

stop bits

1/2

1

 

 

 

parity

none/odd/even

even

 

 

 

Modbus communications mode

RTU/ASCII

RTU

 

 

 

Note: To restore all of the CFG port’s communication parameters to their factory default settings, push the RST button (See The RST Button, p. 55) on the NIM. Be aware, however, that this action will overwrite all of the island’s current configuration values with factory default values.

You can also password protect a configuration, thereby putting the island in protected mode (See Protecting Configuration Data, p. 164). If you do this, however, the RST button will be disabled and you will not be able to use it to reset the port parameters.

890USE17700 April 2004

33