Schneider Electric 890USE17700 manual Restoring Default Parameters from the Web, Reboot Option, p

Models: 890USE17700

1 194
Download 194 pages 47.07 Kb
Page 75
Image 75
Restoring Default Parameters from the Web

STB NIP 2212 Web Server

Restoring Default Parameters from the Web

Use the following procedure to reconfigure the STB NIP 2212 with its default

IP parameters (See Deriving an IP Address from a Media Access Control (MAC) Address, p. 61) from the web. Note: Your STB NIP 2212 cannot have a role name.

Step

Action

Comment

 

 

 

 

 

1

Open the STB NIP 2212 web site.

 

 

 

 

 

 

2

Click on the Configuration tab to display

 

 

 

the Configuration menu.

 

 

 

 

 

 

3

Select the Configured IP option.

The Configured IP web page (See Sample

 

 

 

Configured IP Web Page, p. 72) opens.

 

 

 

 

 

4

Click on the Default button.

The IP address parameters are restored

 

 

 

to their default values.

 

 

 

The address is based on the 48-bit MAC

 

 

 

address that was programmed into the

 

 

 

STB NIP 2212 when it was manufactured.

 

 

 

 

 

5

Click on the Save button to save the

Note: The LAN ST LED (See Ethernet

 

 

address to Flash memory and in RAM.

Communications LEDs, p. 31) on the NIM

 

 

 

blinks six times if the STB NIP 2212

 

 

 

default address is in use. If the address is

 

 

 

a duplicate, the LAN ST LED blinks four

 

 

 

times.

 

 

 

 

 

6

Click on the Configuration tab to return

 

 

 

to the Configuration menu.

 

 

 

 

 

 

7

Select the Reboot option (See About the

 

 

 

Reboot Option, p. 76).

 

 

 

 

 

 

8

At the Reboot now? prompt, click on the

 

 

 

OK button.

 

 

 

 

 

 

9

Click on the OK button at the

 

 

 

confirmation prompt, "Are you sure?"

 

 

 

 

 

 

 

 

 

 

890USE17700 April 2004

75

Page 75
Image 75
Schneider Electric 890USE17700 manual Restoring Default Parameters from the Web, Configured IP Web Page, p. 72 opens