Schneider Electric 890USE17700 mandatory stop will load the island’s default configuration data

Models: 890USE17700

1 194
Download 194 pages 47.07 Kb
Page 154
Image 154
mandatory stop will load the island’s default configuration data.

Advanced Configuration Features

Recovering from

Pushing the RST button (See The RST Button, p. 55) while recovering from a

a Mandatory

mandatory stop will load the island’s default configuration data.

Stop

 

 

 

 

 

 

 

WARNING

 

 

 

 

 

UNINTENDED EQUIPMENT OPERATION/LOSS OF

 

 

CONFIGURATION—RST BUTTON WHILE RECOVERING FROM

 

 

MANDATORY STOP

 

 

Pushing the RST button (See The RST Button, p. 55) causes the island

 

 

bus to reconfigure itself with factory-default operating parameters,

 

 

which do not support mandatory I/O status.

 

 

￿Do not attempt to restart the island by pushing the RST button.

 

 

If a module is unhealthy, replace it with the same module type.

 

 

Failure to follow this precaution can result in death, serious injury,

 

 

or equipment damage.

 

 

 

 

 

 

Hot Swapping a

If the NIM has stopped island bus operations because it cannot detect a healthy

Mandatory

mandatory module, you can recover island bus operations by installing a healthy

Module

module of the same type. The NIM automatically configures the replacement module

 

to match the removed module. Assuming that other modules and devices on the

 

island bus are correctly configured and conform to their configuration data as written

 

to Flash memory, the NIM will start/restart normal island bus operations.

 

 

 

Note: When hot swapping a mandatory module with a Fipio NIM present, the

 

hardware configuration fault bit (x5) in the standard channel status is set.

 

Replacing the module does not clear the bit. To restore normal operations in

 

accordance with Fipio standards, reset the NIM with a reset command from the

 

fieldbus or cycle NIM power.

 

 

 

 

 

 

154

890USE17700 April 2004

Page 154
Image 154
Schneider Electric 890USE17700 manual mandatory stop will load the island’s default configuration data