3-5 Alarms
Reviewing Alarms
At the Station Status or Pump Status screen:
1.Touch Alarms.
The Alarm Log screen appears, with the newest alarm listed first:
To scroll up and down through the list:
•Touch ▲ and ▼ at the bottom of the list.
Silencing Alarms
Whenever a new alarm occurs, your controller sounds the horn and turns on the strobe light at each central alarm. If the alarm is for a specific station or pump, and if the station or pump has a local alarm, the controller also turns on the local alarm light. In addition, a banner appears on the touch screen displaying an alarm message and a Push To Silence button.
To silence the alarm:
1.Touch Push to Silence on the alarm banner.
The horns and lights at the central alarms turn off. (The local alarm light stays on.) The banner will close. Your controller has separate, configurable settings for how long the horns should remain silent and how long the lights should remain off. If the alarm condition still exists when either of these times elapses, the corresponding devices (horns or lights) turn on again. If a new alarm occurs, both the horns and the lights turn on.
Chapter 4: Operation | 62 |