Slot A

Slot B

 

 

 

 

 

 

 

 

 

 

Output

 

Terminal Function

Configuration

 

 

 

 

 

 

 

1

2

3

 

4

 

 

 

 

 

 

 

 

 

X1

 

X3

 

 

common (Any switched dc output can use this common.)

Switched dc/open collector

W1

 

W3

 

 

dc- (open collector)

output 1: PM6 _ _ C _-_ _ _ _ A _ _

Y1

 

Y3

 

 

dc+

output 3: PM6 _ _ _ _-_ _ C _ A _ _

 

 

 

 

 

 

 

W2

 

W4

dc-

Switched dc

 

Y2

 

 

Y4

dc+

output 2: PM6 _ _ _ C-_ _ _ _ A _ _

 

 

 

 

 

 

output 4: PM6 _ _ _ _-_ _ _ C A _ _

 

 

 

 

 

 

 

F1

 

F3

 

 

voltage or current -

Universal Process

G1

 

G3

 

 

voltage +

output 1: PM6 _ _ F _-_ _ _ _ A _ _

H1

 

H3

 

 

current +

output 3: PM6 _ _ _ _-_ _ F _ A _ _

 

 

 

 

 

 

 

L1

 

L3

 

 

normally open

Mechanical Relay 5 A, Form C

K1

 

K3

 

 

common

output 1: PM6 _ _ E _-_ _ _ _ A _ _

J1

 

J3

 

 

normally closed

output 3: PM6 _ _ _ _-_ _ E _ A _ _

 

 

 

 

 

 

 

 

L2

 

 

 

normally open

No-arc 15 A, Form A

 

K2

 

 

 

common

output 2: PM6 _ _ _ H-_ _ _ _ A _ _

 

 

 

 

 

 

 

 

L2

 

 

L4

normally open

Mechanical Relay 5 A, Form A

 

K2

 

 

K4

common

output 2: PM6 _ _ _ J-_ _ _ _ A _ _

 

 

 

 

 

 

output 4: PM6 _ _ _ _-_ _ _ J A _ _

 

 

 

 

 

 

 

L1

L2

L3

 

L4

normally open

Solid-state Relay 0.5 A, Form A

K1

K2

K3

 

K4

common

output 1: PM6 _ _ K _-_ _ _ _ A _ _

 

 

 

 

 

 

output 2: PM6 _ _ _ K-_ _ _ _ A _ _

 

 

 

 

 

 

output 3: PM6 _ _ _ _-_ _ K _ A _ _

 

 

 

 

 

 

output 4: PM6 _ _ _ _-_ _ _ K A _ _

 

 

 

 

 

 

Communications

 

 

 

 

 

 

 

 

 

 

CB

 

Modbus RTU EIA-485 T+/R+

Modbus RTU 232/485 Communications

 

 

CA

 

Modbus RTU EIA-485 T-/R-

PM6 _ _ _ _-2 A A A A _ _

 

 

CC

 

Modbus RTU EIA-485 common

 

 

 

CB

 

Modbus RTU EIA-485 T+/R+

 

 

 

CA

 

Modbus RTU EIA-485 T-/R-

 

 

 

C5

 

Modbus RTU EIA-232 common

 

 

 

C3

 

Modbus RTU EIA-232 to DB9 pin 2

 

 

 

C2

 

Modbus RTU EIA-232 to DB9 pin 3

 

 

 

 

 

 

 

 

 

V+

 

DeviceNet™ power

DeviceNet™ Communications

 

 

CH

Positive side of DeviceNet™ bus

PM6 _ _ _ _-5 A A A A _ _

 

 

SH

 

Shield interconnect

 

 

 

CL

 

Negative side of DeviceNet™ bus

 

 

 

V-

 

DeviceNet™ power return

 

 

 

 

 

 

 

 

 

E8

 

EtherNet/IP™ and Modbus TCP unused

Ethernet 10/100 supporting EtherNet/IP™

 

 

E7

 

EtherNet/IP™ and Modbus TCP unused

and Modbus TCP

 

 

E6

 

EtherNet/IP™ and Modbus TCP receive -

PM6 _ _ _ _-3 A A A A _ _

 

 

E5

 

EtherNet/IP™ and Modbus TCP unused

 

 

 

E4

 

EtherNet/IP™ and Modbus TCP unused

 

 

 

E3

 

EtherNet/IP™ and Modbus TCP receive +

 

 

 

E2

 

EtherNet/IP™ and Modbus TCP transmit -

 

 

 

E1

 

EtherNet/IP™ and Modbus TCP transmit +

 

 

 

 

 

 

 

 

Inputs

12

T1

T2

S2

(RTD) or current +, potentiometer wiper

Universal Sensor

S1

S2

S3

(RTD), thermocouple -, current - or volts -

input 1: all configurations

R1

R2

S1

(RTD), thermocouple + or volts +

input 2: PM6 _ _ _ _-_ (R or L) _ _ A _ _

 

 

 

 

 

 

 

 

 

T2

mA ac

Current Transformer

 

S2

mA ac

PM6 _ _ _ _-_ T _ _ A _ _

Terminal Definitions for Slots A and B.

Slot A

1 Input 2 Output 1 Output

Slot B

Slot C

Output

Power

4 Output 3

485 Comms

2 Input

I/O 5 & 6

 

Dig

Slot B

Communications

or

Watlow EZ-ZONE®PM Integrated Controller

11