Indication

Description

Possible Cause(s)

Corrective Action

 

 

 

 

Process doesn’t con-

Process is unstable or never

• Controller not tuned correctly

• Perform autotune or manually tune

trol to set point

reaches set point

 

system

 

 

• Control mode is incorrectly set

• Set control mode appropriately (Open

 

 

 

vs Closed Loop)

 

 

• Control set point is incorrect

• Set control set point in appropriate

 

 

 

control mode and check source of set

 

 

 

point: remote, idle, profile, closed loop,

 

 

 

open loop

 

 

 

 

Temperature runway

Process value continues to

• Controller output incorrectly pro-

• Verify output function is correct (heat

 

increase or decrease past set

grammed

or cool)

 

point.

 

 

 

 

• Thermocouple reverse wired

• Correct sensor wiring (red wire nega-

 

 

 

tive)

 

 

• Controller output wired incorrectly

• Verify and correct wiring

 

 

• Short in heater

• Replace heater

 

 

• Power controller connection to con-

• Replace or repair power controller

 

 

troller defective

 

 

 

• Controller output defective

• Replace or repair controller

 

 

 

 

[`100] Device Error

Controller displays internal

• Controller defective

• Replace or repair controller

[rEtn]

malfunction message at

 

 

 

power up.

 

 

 

 

 

 

[`h;Er] Heater Error

Heater Error

• Current through load is above current

• Check that the load current is proper.

 

 

trip set point

Correct cause of overcurrent and/or en-

 

 

 

sure current trip set point is correct.

 

 

• Current through load is below current

• Check that the load current is proper.

 

 

trip set point

Correct cause of undercurrent and/or

 

 

 

ensure current trip set point is correct.

 

 

 

 

[`C;Er]

Load current incorrect.

• Shorted solid-state or mechanical

• Replace relay

Current Error

 

relay

 

 

 

• Open solid-state or mechanical relay

• Replace relay

 

 

• Current transformer load wire associ-

• Route load wire through current

 

 

ated to wrong output

transformer from correct output, and

 

 

 

go to the [`C;Si] Source Output In-

 

 

 

stance parameter (Setup Page, Current

 

 

 

Menu) to select the output that is driv-

 

 

 

ing the load.

 

 

• Defective current transformer or con-

• Replace or repair sensor or controller

 

 

troller

 

 

 

• Noisy electrical lines

• Route wires appropriately, check for

 

 

 

loose connections, add line filters

 

 

 

 

Menus inaccessible

Unable to access [`SEt],

• Security set to incorrect level

• Check lockout setting in Factory Page

 

[OPEr], [FCty] or [ProF]

 

 

 

menus or particular prompts

 

 

 

in Home Page

 

 

 

 

• Digital input set to lockout keypad

• Change state of digital input

 

 

• Custom parameters incorrect

• Change custom parameters in Factory

 

 

 

Page

 

 

 

 

EZ-Key doesn’t work

EZ-Key does not activate re-

EZ-Key function incorrect

• Verify EZ-Key function in Setup Menu

 

quired function

 

 

 

 

EZ-Key function instance not incor-

• Check that the function instance is

 

 

rect

correct

 

 

• Keypad malfunction

• Replace or repair controller

 

 

 

 