Indication | Description | Possible Cause(s) | Corrective Action |
|
|
|
|
Process doesn’t con- | Process is unstable or never | • Controller not tuned correctly | • Perform autotune or manually tune |
trol to set point | reaches set point |
| system |
|
| • Control mode is incorrectly set | • Set control mode appropriately (Open |
|
|
| vs Closed Loop) |
|
| • Control set point is incorrect | • Set control set point in appropriate |
|
|
| control mode and check source of set |
|
|
| point: remote, idle, profile, closed loop, |
|
|
| open loop |
|
|
|
|
Temperature runway | Process value continues to | • Controller output incorrectly pro- | • Verify output function is correct (heat |
| increase or decrease past set | grammed | or cool) |
| point. |
|
|
|
| • Thermocouple reverse wired | • Correct sensor wiring (red wire nega- |
|
|
| tive) |
|
| • Controller output wired incorrectly | • Verify and correct wiring |
|
| • Short in heater | • Replace heater |
|
| • Power controller connection to con- | • Replace or repair power controller |
|
| troller defective |
|
|
| • Controller output defective | • Replace or repair controller |
|
|
|
|
[`100] Device Error | Controller displays internal | • Controller defective | • Replace or repair controller |
[rEtn] | malfunction message at |
|
|
| power up. |
|
|
|
|
|
|
[`h;Er] Heater Error | Heater Error | • Current through load is above current | • Check that the load current is proper. |
|
| trip set point | Correct cause of overcurrent and/or en- |
|
|
| sure current trip set point is correct. |
|
| • Current through load is below current | • Check that the load current is proper. |
|
| trip set point | Correct cause of undercurrent and/or |
|
|
| ensure current trip set point is correct. |
|
|
|
|
[`C;Er] | Load current incorrect. | • Shorted | • Replace relay |
Current Error |
| relay |
|
|
| • Open | • Replace relay |
|
| • Current transformer load wire associ- | • Route load wire through current |
|
| ated to wrong output | transformer from correct output, and |
|
|
| go to the [`C;Si] Source Output In- |
|
|
| stance parameter (Setup Page, Current |
|
|
| Menu) to select the output that is driv- |
|
|
| ing the load. |
|
| • Defective current transformer or con- | • Replace or repair sensor or controller |
|
| troller |
|
|
| • Noisy electrical lines | • Route wires appropriately, check for |
|
|
| loose connections, add line filters |
|
|
|
|
Menus inaccessible | Unable to access [`SEt], | • Security set to incorrect level | • Check lockout setting in Factory Page |
| [OPEr], [FCty] or [ProF] |
|
|
| menus or particular prompts |
|
|
| in Home Page |
|
|
|
| • Digital input set to lockout keypad | • Change state of digital input |
|
| • Custom parameters incorrect | • Change custom parameters in Factory |
|
|
| Page |
|
|
|
|
• | • Verify | ||
| quired function |
|
|
|
| • | • Check that the function instance is |
|
| rect | correct |
|
| • Keypad malfunction | • Replace or repair controller |
|
|
|
|
Watlow | • 68 • | Appendix |