Dis- | Parameter Name | Set- | Range | Default | Appears If |
play | Description | tings |
|
|
|
[`A;hy] | Alarm (1 to 4) |
| 0.001 to 9,999.000°F or units | 1.0°F or units | always |
[ A.hy] | Hysteresis |
| 0.001 to 5,555.000°C | 1.0°C |
|
| Set the hysteresis for an alarm. This de- |
|
|
|
|
| termines how far into the safe region the |
|
|
|
|
| process value needs to move before the |
|
|
|
|
| alarm can be cleared. |
|
|
|
|
|
|
|
|
|
|
[`A;Lg] | Alarm (1 to 4) |
| [`AL;C] Close On Alarm | Close On | always |
[ A.Lg] | Logic |
| [`AL;o] Open On Alarm | Alarm |
|
| Select what the output condition will be |
|
|
|
|
| during the alarm state. |
|
|
|
|
|
|
|
|
|
|
[`A;Sd] | Alarm (1 to 4) |
| [both] Both | Both | always |
[ A.Sd] | Sides |
| [high] High |
|
|
| Select which side or sides will trigger this |
| [LoW] Low |
|
|
| alarm. |
|
|
| |
|
|
|
|
| |
|
|
|
|
|
|
[`A;LA] | Alarm (1 to 4) |
| [nLAt] | always | |
[ A.LA] | Latching |
| [`LAt] Latching |
|
|
| Turn alarm latching on or off. A latched |
|
|
|
|
| alarm has to be turned off by the user. |
|
|
|
|
|
|
|
|
|
|
[`A;bL] | Alarm (1 to 4) |
| [`oFF] Off | Off | always |
[ A.bL] | Blocking |
| [`Str] Startup |
|
|
| Select when an alarm will be blocked. |
| [StPt] Set Point |
|
|
| After startup and/or after the set point |
|
|
| |
|
| [both] Both |
|
| |
| changes, the alarm will be blocked until |
|
|
| |
|
|
|
|
| |
| the process value enters the normal range. |
|
|
|
|
|
|
|
|
|
|
[`A;Si] | Alarm (1 to 4) |
| [`oFF] Off | Off | always |
[ A.Si] | Silencing |
| [``on] On |
|
|
| Turn alarm silencing on to allow the user |
|
|
|
|
| to disable this alarm. |
|
|
|
|
|
|
|
|
|
|
[A;dSP] | Alarm (1 to 4) |
| [`oFF] Off | On | always |
[A.dSP] | Display |
| [``on] On |
|
|
| Display an alarm message when an alarm |
|
|
|
|
| is active. |
|
|
|
|
|
|
|
|
|
|
[`A;dL] | Alarm (1 to 4) |
| 0 to 9,999 seconds | 0 | always |
[ A.dL] | Delay |
|
|
|
|
| Set the time the alarm will be delayed |
|
|
|
|
| after the process value exceeds the alarm |
|
|
|
|
| set point. |
|
|
|
|
|
|
|
|
|
|
[CUrr] |
|
|
|
|
|
[`Set] |
|
|
|
|
|
Current Menu (menu appears if PM6 _ _ _ |
|
|
| ||
|
|
|
|
|
|
[`C;Sd] | Current |
| [`oFF] Off | Off | always |
[ C.Sd] | Sides |
| [high] High |
|
|
| Select which side of the current to monitor. |
| [LoW] Low |
|
|
|
|
|
|
| |
|
|
| [both] Both |
|
|
|
|
|
|
|
|
[`CU;r] | Current |
| [``no] No | No | always |
[ CU.r] | Reading Enable |
| [`YES} Yes |
|
|
| Display under- or |
|
|
|
|
[`C;dt] | Current |
| 3 to 59 | 9 | always |
[ C.dt] | Detect Threshold |
|
|
|
|
| For factory adjustment only. |
|
|
|
|
|
|
|
|
|
|
[`C;SC] | Current |
| 0 to 9,999.000 amperes | 50.0 | always |
[ C.SC] | Scaling |
|
|
|
|
| Adjust scaling to match the transformer's |
|
|
|
|
| high range. |
|
|
|
|
|
|
|
|
|
|
[C;oFS] | Current |
| 0.0 | always | |
[C.oFS] | Offset |
|
|
|
|
| Calibrate the current reading with an |
|
|
|
|
| offset value. |
|
|
|
|
|
|
|
|
|
|
Note: Some values will be rounded off to fit in the
Watlow | • 41 • | Chapter 6 Setup Page |