Dis-

Parameter Name

Set-

Range

Default

Appears If

play

Description

tings

 

 

 

[`A;hy]

Alarm (1 to 4)

 

0.001 to 9,999.000°F or units

1.0°F or units

always

[ A.hy]

Hysteresis

 

0.001 to 5,555.000°C

1.0°C

 

 

Set the hysteresis for an alarm. This de-

 

 

 

 

 

termines how far into the safe region the

 

 

 

 

 

process value needs to move before the

 

 

 

 

 

alarm can be cleared.

 

 

 

 

 

 

 

 

 

 

[`A;Lg]

Alarm (1 to 4)

 

[`AL;C] Close On Alarm

Close On

always

[ A.Lg]

Logic

 

[`AL;o] Open On Alarm

Alarm

 

 

Select what the output condition will be

 

 

 

 

 

during the alarm state.

 

 

 

 

 

 

 

 

 

 

[`A;Sd]

Alarm (1 to 4)

 

[both] Both

Both

always

[ A.Sd]

Sides

 

[high] High

 

 

 

Select which side or sides will trigger this

 

[LoW] Low

 

 

 

alarm.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[`A;LA]

Alarm (1 to 4)

 

[nLAt] Non-Latching

Non-Latching

always

[ A.LA]

Latching

 

[`LAt] Latching

 

 

 

Turn alarm latching on or off. A latched

 

 

 

 

 

alarm has to be turned off by the user.

 

 

 

 

 

 

 

 

 

 

[`A;bL]

Alarm (1 to 4)

 

[`oFF] Off

Off

always

[ A.bL]

Blocking

 

[`Str] Startup

 

 

 

Select when an alarm will be blocked.

 

[StPt] Set Point

 

 

 

After startup and/or after the set point

 

 

 

 

 

[both] Both

 

 

 

changes, the alarm will be blocked until

 

 

 

 

 

 

 

 

 

the process value enters the normal range.

 

 

 

 

 

 

 

 

 

 

[`A;Si]

Alarm (1 to 4)

 

[`oFF] Off

Off

always

[ A.Si]

Silencing

 

[``on] On

 

 

 

Turn alarm silencing on to allow the user

 

 

 

 

 

to disable this alarm.

 

 

 

 

 

 

 

 

 

 

[A;dSP]

Alarm (1 to 4)

 

[`oFF] Off

On

always

[A.dSP]

Display

 

[``on] On

 

 

 

Display an alarm message when an alarm

 

 

 

 

 

is active.

 

 

 

 

 

 

 

 

 

 

[`A;dL]

Alarm (1 to 4)

 

0 to 9,999 seconds

0

always

[ A.dL]

Delay

 

 

 

 

 

Set the time the alarm will be delayed

 

 

 

 

 

after the process value exceeds the alarm

 

 

 

 

 

set point.

 

 

 

 

 

 

 

 

 

 

[CUrr]

 

 

 

 

 

[`Set]

 

 

 

 

 

Current Menu (menu appears if PM6 _ _ _ _-_ T _ _ A _ _)

 

 

 

 

 

 

 

 

 

[`C;Sd]

Current

 

[`oFF] Off

Off

always

[ C.Sd]

Sides

 

[high] High

 

 

 

Select which side of the current to monitor.

 

[LoW] Low

 

 

 

 

 

 

 

 

 

 

[both] Both

 

 

 

 

 

 

 

 

[`CU;r]

Current

 

[``no] No

No

always

[ CU.r]

Reading Enable

 

[`YES} Yes

 

 

 

Display under- or over-range current.

 

 

 

 

[`C;dt]

Current

 

3 to 59

9

always

[ C.dt]

Detect Threshold

 

 

 

 

 

For factory adjustment only.

 

 

 

 

 

 

 

 

 

 

[`C;SC]

Current

 

0 to 9,999.000 amperes

50.0

always

[ C.SC]

Scaling

 

 

 

 

 

Adjust scaling to match the transformer's

 

 

 

 

 

high range.

 

 

 

 

 

 

 

 

 

 

[C;oFS]

Current

 

-1,999.000 to 9,999.000

0.0

always

[C.oFS]

Offset

 

 

 

 

 

Calibrate the current reading with an

 

 

 

 

 

offset value.

 

 

 

 

 

 

 

 

 

 

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces. If there is only one instance of a menu, no submenus will appear.

Watlow EZ-ZONE®PM Integrated Controller

41

Chapter 6 Setup Page