Output 4 Solid-state Relay, Form A
Warning:
Use National Electric (NEC)
Slot B
L3
K3
• 0.5 A at 20 to 264VÅ (ac) maxi- |
mum resistive load |
• 20 VA 120/240VÅ (ac) pilot duty |
or other
normally open
J3
L4
• |
suppression |
• maximum off state leakage of |
normally L4 open
K4
connecting this controller to a power source and to electrical sensors or peripheral devices. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.
Note:
Maximum wire size termination and torque rating:
•0.0507 to 3.30 mm2 (30 to
12 AWG)
•0.8 Nm (7.0
Note:
Adjacent terminals may be labeled differently, depending on the model number.
Note:
To prevent damage to the controller, do not connect wires to unused terminals.
Note:
Maintain electrical isolation between analog input 1, digital
Note:
The control output common terminal and the digital common terminal are referenced to different voltages and must remain isolated.
Quencharc Note:
Switching pilot duty inductive loads (relay coils, solenoids, etc.) with the mechanical relay, solid state relay or open collector output options requires use of an R.C. sup- pressor.
common
K4
T2
S2
R2
| 105 microamperes |
• | Output does not supply power. |
• | Do not use on dc loads. |
See Quencharc note. PM6 _ _ _
common
Internal Circuitry