Output 4 Solid-state Relay, Form A

Warning:

Use National Electric (NEC)

Slot B

L3

K3

• 0.5 A at 20 to 264VÅ (ac) maxi-

mum resistive load

• 20 VA 120/240VÅ (ac) pilot duty

or other country-specific standard wiring and safety practices when wiring and

normally open

J3

L4

opto-isolated, without contact

suppression

• maximum off state leakage of

Solid-state Relay

normally L4 open

K4

connecting this controller to a power source and to electrical sensors or peripheral devices. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.

Note:

Maximum wire size termination and torque rating:

0.0507 to 3.30 mm2 (30 to

12 AWG) single-wire termi- nation or two 1.31 mm2 (16 AWG)

0.8 Nm (7.0 lb.-in.) torque

Note:

Adjacent terminals may be labeled differently, depending on the model number.

Note:

To prevent damage to the controller, do not connect wires to unused terminals.

Note:

Maintain electrical isolation between analog input 1, digital input-outputs, switched dc/open collector outputs and process outputs to prevent ground loops.

Note:

The control output common terminal and the digital common terminal are referenced to different voltages and must remain isolated.

Quencharc Note:

Switching pilot duty inductive loads (relay coils, solenoids, etc.) with the mechanical relay, solid state relay or open collector output options requires use of an R.C. sup- pressor.

common

K4

T2

S2

R2

 

105 microamperes

Output does not supply power.

Do not use on dc loads.

See Quencharc note. PM6 _ _ _ _-_ _ _ K A _ _

common

Internal Circuitry

Watlow EZ-ZONE®PM Integrated Controller

21

Chapter 2 Install and Wire