Dis-

 

Parameter Name

Set-

Range

Default

Appears If

 

play

 

Description

tings

 

 

 

[`leu]

Digital Input (5 or 6)

 

[high] High

High

Direction is set to Input

[

LEu]

Level

 

 

[Low] Low

 

Voltage or Input Dry

 

 

Select what action will be interpreted as a

 

 

 

Contact.

 

 

true state.

 

 

 

 

 

 

 

 

 

 

 

[``Fn]

Digital Input (5 or 6)

 

[none] None

None

Direction is set to Input

[

Fn]

Function

 

 

[idLE] Idle Set Point Enable

 

Voltage or Input Dry

 

 

Select the function that will be triggered

 

(level)

 

Contact, and the fea-

 

 

by a true state.

 

[tUnE] Tune (edge)

 

ture is available.

 

 

Functions respond to a level state change

 

 

 

 

 

 

[ALM] Alarm Reset (edge)

 

 

 

 

or an edge level change.

 

 

 

 

 

 

[`SiL] Silence Alarms (edge)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[MAn] Manual/Auto Mode

 

 

 

 

 

 

 

(level)

 

 

 

 

 

 

 

[`oFF] Control Outputs Off

 

 

 

 

 

 

 

(level)

 

 

 

 

 

 

 

[`r;En] Remote Set Point En-

 

 

 

 

 

 

 

able (level)

 

 

 

 

 

 

 

[P;LoC] Lock Keypad (level)

 

 

 

 

 

 

 

[`F;AL] Force Alarm (level)

 

 

 

 

 

 

 

[`t;dA] TRU-TUNE+®Dis-

 

 

 

 

 

 

 

able (level)

 

 

 

 

 

 

 

[`AoF] Alarm Outputs &

 

 

 

 

 

 

 

Control Loop Off (level)

 

 

 

 

 

 

 

[USr;r] Restore User Settings

 

 

 

 

 

 

 

(edge)

 

 

 

 

 

 

 

[P;diS] Profile Disable (level)

 

 

 

 

 

 

 

[P;hoL] Profile Hold/Resume

 

 

 

 

 

 

 

(level)

 

 

 

 

 

 

 

[ProF] Profile Start Number

 

 

 

 

 

 

 

(edge)

 

 

 

 

 

 

 

[P;StS] Profile Start/Stop

 

 

 

 

 

 

 

(level)

 

 

 

 

 

 

 

[LMr] Limit Reset (edge)

 

 

 

 

 

 

 

 

[``Fi]

Digital Input (5 or 6)

 

0 All Instances (except pro-

1

Direction is set to Input

[

Fi]

Function Instance

 

files)

 

Voltage or Input Dry

 

 

Select which instance of the Event Func-

 

(For example, if Digital Func-

 

Contact, and there is

 

 

tion will be triggered by a true state.

 

tion is set to Silence Alarms

 

more than one instance

 

 

 

 

 

and Function Instance is set

 

of the Function selec-

 

 

 

 

 

to 0, then this digital input

 

tion.

 

 

 

 

 

will silence all alarms.)

 

 

 

 

 

 

 

1 to 4

 

 

 

 

 

 

 

 

 

[LIm]

 

 

 

 

 

 

[`Set]

 

 

 

 

 

 

Limit Menu

(menu apprears if PM6 _ _ _ _-_ L _ _ AAA)

 

 

 

 

 

 

 

 

 

[`L;Sd]

Limit

 

 

[both] Both

Both

always

[ L.Sd]

Sides

 

 

[high] High

 

 

 

 

Select which side or sides of the process

 

[LoW] Low

 

 

 

 

value will be monitored.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[`L;hy]

Limit

 

 

0.001 to 9,999.000°F or units

3.0°F or units

always

[ L.hy]

Hysteresis

 

 

0.001 to 5,555.000°C

2.0°C

 

 

 

Set the hysteresis for the limit function.

 

 

 

 

 

 

This determines how far into the safe

 

 

 

 

 

 

range the process value must move before

 

 

 

 

 

 

the limit turns the output back on.

 

 

 

 

 

 

 

 

 

 

 

sp;lh

Limit

 

 

-1999.000 - 9999.000

9999.000

always

[ SP.Lh]

Set Point Limit High

 

 

 

 

 

 

Clamp the operational limit high maxi-

 

 

 

 

 

 

mum setting to this value.

 

 

 

 

 

 

 

 

 

 

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.

 

If there is only one instance of a menu, no submenus will appear.

 

 

 

 

 

 

 

 

 

 

 

Watlow EZ-ZONE®PM Integrated Controller

36

Chapter 6 Setup Page