Specifications

Line Voltage/Power

85 to 264VÅ (ac), 47 to 63 Hz

12 to 40VÎ (dc); 20 to 28VÅ (ac), 47 to 63 Hz

10VA maximum power consumption

Data retention upon power failure via nonvolatile memory

Compliant with Semi F47-0200, Figure R1-1 voltage sag require- ments @ 24Å (ac) or higher

Environment

-18 to 65°C (0 to 149°F) operating temperature

-40 to 85°C (-40 to 185°F) storage temperature

0 to 90 percent RH, non-condensing

Accuracy

Calibration accuracy and sensor conformity: ±0.1 percent of ac- curacy span, ±1°C at the calibrated ambient temperature and rated line voltage

Types R, S, B; 0.2 percent

Type T below -50°C (58°F); 0.2 percent

Calibration ambient temperature @ 25°C, ±3°C (77°F, ±5°F)

Accuracy span: 540°C (1,000°F) minimum

Temperature stability: ±0.1°C/°C (±0.1°F/°F) rise in ambient maximum

Process Output: ±15 mV using 0 to 10 VÎ (dc), resolution @ 3 mV and ±30 μA using 0 to 20 mA, resolution @ 6 μA

Agency Approvals

UL® Listed to UL 61010-1 File E185611.

UL Reviewed to CSA C22.2 No. 61010-1-04.

UL 50 Type 4X, NEMA 4X indoor locations, IP66 front panel seal.

FM Class 3545 File 3029084 temperature limit switches.

CE – See Declaration of Conformity. RoHS and W.E.E.E. compliant.

ODVA – EtherNet/IP™ Compliance.

UL® Listed to ANSI/ISA 12.12.01-2001 File E184390.

UL reviewed to CSA C22.2 No. 213-1987.

This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or Non-Hazardous locations only. Temperature Code T4A.

WARNING – EXPLOSION HAZARD. Substitution of component may impair suitability for Class I, Division 2.

WARNING – EXPLOSION HAZARD. Do not disconnect equipment unless power has been switched off or the area is known to be non- hazardous.

Controller

Microprocessor-based, user-selectable control modes

PID module: Single universal input, 2 outputs

Limit module: Single universal input, 2 outputs

2 total additional digital input/outputs shared between PID and limit functions

Control sampling rates: input 10 Hz, outputs 10 Hz

Serial Communications

Isolated communications EIA-485, Standard Bus: all models; EIA-232/485, Modbus™ RTU and Ethernet IP/Modbus™ TCP serial communications. Future options include DeviceNet™ and Profibus™ DP

Wiring Termination, Touch-Safe Terminals

Input, power and controller output terminals touch-safe remov- able 3.30 to 0.0507mm² (12 to 30 AWG)

Wire strip length 7.6 mm (0.30 in)

Torque 0.8 Nm (7.0 lb.- in.)

Universal Input

Thermocouple, grounded or ungrounded sensors >20 MΩ input impedance

Maximum of 2K Ω source resistance

RTD 2- or 3-wire, platinum, 100 and 1,000 Ω @ 0°C calibration to DIN curve (0.00385 Ω/Ω/°C); lead resistance effect: 0.3°C/Ω maximum

Process, 0 to 20 mA @ 100 Ω, or 0 to 10VÎ (dc) and 0 to 50 mV @ 20 kΩ input impedance; scalable

Inverse scaling

Accuracy Range

Type J: 0 to 750°C or 32 to 1,383°F (±1.75°C)

Type K: -200 to 1,250°C or -328 to 2,282°F (±2.45°C)

Type T: -200 to 350°C or -328 to 662°F (±1.55°C)

Type E: -328 to 1,652°C or -200 to 900°F (±2.10°C)

Type N: 0 to 1,250°C or 32 to 2,282°F (±2.25°C)

Type C: 0 to 2,315°C or 32 to 4,199°F (±3.32°C)

Type D: 0 to 2,315°C or 32 to 4,199°F (±3.32°C)

Type F: 0 to 1,343°C or 32 to 2,450°F (±2.39°C)

Type R: 0 to 1,450°C or 32 to 2,642°F (±3.90°C)

Type S: 0 to 1,450°C or 32 to 2,642°F (±3.90°C)

Type B: 870 to 1,700°C or 1,598 to 3,092°F (±2.66°C)

RTD (DIN): -200 to 800°C or -328 to 1,472°F (±2.00°C)

Volts: 0 to 10 (±0.01V)

mA DC: 0 to 20 (±0.02 mA)

mV: 0 to 50 (±0.05 mV)

Potentiometer: 0 to 1,200 Ω (±1.0 Ω)

Functional Operating Range

Type J: -210 to 1,200°C or -346 to 2,192°F

Type K: -200 to 1,370°C or -328 to 2,500°F

Type T: -200 to 400°C or -328 to 750°F

Type E: -200 to 1,000°C or -328 to 1,832°F

Type N: -200 to 1,300°C or -328 to 2,372°F

Type C: 0 to 2,315°C or 32 to 4,200°F

Type D: 0 to 2,315°C or 32 to 4,200°F

Type F: 0 to 1,395°C or 32 to 2,543°F

Type R: -50 to 1,767°C or -58 to 3,214°F

Type S: -50 to 1,767°C or -58 to 3,214°F

Type B: 0 to 1,816°C or 32 to 3,300°F

RTD (DIN): -200 to 800°C or -328 to 1,472°F

Process: -1,999 to 9,999 units

Digital Input

Update rate 10 Hz

Dry contact or dc voltage

DC voltage

Maximum input 36V at 3 mA

Minimum high state 3V @ 0.25 mA

Maximum low state 2V

Dry contact

Minimum open resistance 10 kΩ

Maximum closed resistance 50 Ω

Maximum short circuit 13 mA

Digital Output

Update rate 10 Hz

Output voltage 24V

Current limit, Output 5, 24 mA maximum; Output 6, 10 mA maximum

Current Measurement

Requires optional current transformer 16-0246

Accepts 0 to 50 mA signal (user programmable range) 2 to 50A usable

Displayed operating range and resolution can be scaled and are user programmable.

Output Hardware

User selectable for heat-cool as on-off, P, PI, PD, PID, alarm ac- tion or limit.

Switched DC

Unregulated 22 to 32VÎ (dc) low side @ 30 mA outputs 1 and 3, 10 mA outputs 2 and 4

Open Collector

• Output sink 100 mA @ 30VÎ (dc) maximum

Watlow EZ-ZONE®PM Integrated Controller