Dis- | Parameter Name |
| Set- | Range | Default | Appears If | |
play |
| Description |
| tings |
|
|
|
[`P;EL] | Input (1 or 2) |
|
|
| 0.0 | Sensor Type is set to Mil- | |
[ P.EL] | Process Error Low |
|
|
|
| livolts, Volts, Milliamps | |
| If the process value drops below this value, |
|
|
| or Potentiometer 1 kΩ, | ||
| it will trigger an input error. |
|
|
|
| and Error Enable is set | |
|
|
|
|
|
|
| to Low. |
|
|
|
|
|
|
|
|
[`FiL] | Input (1 or 2) |
|
|
| 0.0 to 60.0 seconds | 0.5 | always |
[ FiL] | Filter Time |
|
|
|
|
|
|
| Filtering smooths out the process signal to |
|
|
|
| ||
| both the display and the input. Increase |
|
|
|
| ||
| the time to increase filtering. |
|
|
|
|
| |
|
|
|
|
|
|
|
|
[`i;Er] | Input (1 or 2) |
|
|
| [`off] Off | Off | always |
[ i.Er] | Error Latching |
|
| [``on] On |
|
| |
| Turn input error latching on or off. If |
|
|
|
|
| |
| latching is on errors must be manually |
|
|
|
| ||
| cleared. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
[`dEC] | Input (1 or 2) |
|
|
| [```0] Whole | Whole | always |
[ dEC] | Decimal |
|
|
| [``0;0] Tenths |
|
|
| Set the precision of the displayed value. |
| [`0;00] Hundredths |
|
| ||
|
|
|
|
|
|
| |
|
|
|
|
| [0;000] Thousandths |
|
|
|
|
|
|
|
|
|
|
[`S;bA] | Input 1 |
|
|
| [`oFF] Off | Off | PM6 _ _ _ |
[ S.bA] | Sensor Backup Enable |
|
| [``on] On |
|
| |
| If the input 1 sensor fails, the controller |
|
|
|
| ||
| will use the input 2 sensor. |
|
|
|
|
| |
|
|
|
|
|
|
|
|
[`dio] |
| [```5] | [```6] |
|
|
| |
[`Set] |
| [`dio] | [`dio] |
|
|
| |
Digital Input/ | Digital Input or | Digital Input or |
|
| |||
Output Menu | Output 5 | Output 6 | (menu appears if PM6 _ [2 or 4] _ | ||||
|
|
|
|
|
|
| |
[`dir] | Digital Input/Output (5 or 6) |
|
| [OtPt] Output | Output | always | |
[ dir] | Direction |
|
|
| [``in] Input Voltage |
|
|
| Set the function to an input or output. |
|
| [iCon] Input Dry Contact |
|
| |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| |
[``Fn] | Digital Output (5 or 6) |
|
| [`oFF] Off | Off | Direction is set to Out- | |
[ Fn] | Function |
|
|
| [CooL] Cool |
| put. |
| Select what function will drive this output. |
| [hEAt] Heat |
|
| ||
|
|
|
|
|
|
| |
|
|
|
|
| [ALM] Alarm |
|
|
|
|
|
|
| [`Ent] Event |
|
|
|
|
|
|
|
|
| |
[`o;Ct] | Digital Output (5 or 6) |
|
| [`Ftb] Fixed Time Base | Fixed Time | Direction is set to Out- | |
[ o.Ct] | Control |
|
|
| [`utb] Variable Time Base | Base | put. |
| Set the output control type. This param- |
|
|
|
| ||
| eter is only used with PID control, but can |
|
|
|
| ||
| be set anytime. |
|
|
|
|
| |
|
|
|
|
|
|
| |
[`o;tb] | Digital Output (5 or 6) |
|
| 0.1 to 60.0 seconds (solid- | 0.1 sec. [SSR & | Control is set to Fixed | |
[ o.tb] | Time Base |
|
|
| state relay or switched dc) | sw dc] | Time Base. |
| Set the time base for |
| 5.0 to 60.0 seconds (mechani- | 20.0 sec. |
| ||
| trol. |
|
|
| cal relay or | [mech, relay, |
|
|
|
|
|
| control) |
| |
|
|
|
|
|
|
| |
[`o;Lo] | Digital Output (5 or 6) |
|
| 0.0 to 100.0% | 0.0% | Direction is set to Output | |
[ o.Lo] | Low Power Scale |
|
|
|
| and Source is set to | |
| The power output will never be less than |
|
|
| Heat or Cool. | ||
| the value specified and will represent the |
|
|
|
| ||
| value at which output scaling begins. |
|
|
|
|
| |
|
|
|
|
|
|
| |
[`o;hi] | Digital Output (5 or 6) |
|
| 0.0 to 100.0% | 100.0% | Direction is set to Output | |
[ o.hi] | High Power Scale |
|
|
|
| and Source is set to | |
| The power output will never be greater |
|
|
| Heat or Cool. | ||
| than the value specified and will represent |
|
|
|
| ||
| the value at which output scaling stops. |
|
|
|
| ||
|
|
|
|
|
|
| |
[``Fi] | Digital Output (5 or 6) |
|
| 1 to 4 | None | Direction is set to Out- | |
[ Fi] | Function Instance |
|
|
|
| put, and there is more | |
| Select which source instance will drive the |
|
|
| than one instance of the | ||
| output. |
|
|
|
|
| Function selection. |
|
|
|
|
|
|
|
|
Note: Some values will be rounded off to fit in the
Watlow | • 35 • | Chapter 6 Setup Page |