Display

 

Parameter name

 

Set-

 

Range

Default

Appears If

 

 

Description

 

tings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[``dB]

Loop

 

 

 

 

 

-1,000.0 to 1,000.0°F or units

0.0

Heat Algorithm

[ db]

Dead Band

 

 

 

 

-556 to 556°C

 

and Cool Algo-

 

Set the offset to the proportional band. With a

 

 

 

 

rithm (Setup

 

negative value, both heating and cooling outputs

 

 

 

 

Page) are set to

 

are active when the process value is near the set

 

 

 

 

PID or On-Off.

 

point. A positive value keeps heating and cooling

 

 

 

 

 

 

outputs from fighting each other.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[`o;SP]

Loop

 

 

 

 

 

-100 to 100% (heat and cool)

0.0

always

[ o.SP]

Open Loop Set Point

 

 

 

0 to 100% (heat only)

 

 

 

Set a fixed level of output power when in manual

 

 

-100 to 0% (cool only)

 

 

 

(open-loop) mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[ALM]

 

[```1]

[```2]

[```3]

[```4]

 

 

 

[oPEr]

 

[ALM]

[ALM]

[ALM]

[ALM]

 

 

 

Alarm Menu

Alarm 1

Alarm 2

Alarm 3

Alarm 4

 

 

 

 

 

 

 

 

 

 

 

[`A;Lo]

Alarm (1 to 4)

 

 

 

 

-1,999.000 to 9,999.000°F or units

32.0°F

Alarm Sides

[ A.Lo]

Low Set Point

 

 

 

 

-1,128.000 to 5,537.000°C

or units

(Setup Page) is

 

If Alarm Type (Setup Page, Alarm Menu) is set to:

 

 

 

0.0°C

not set to High.

 

process - set the process value that will trigger a

 

 

 

 

 

 

low alarm.

 

 

 

 

 

 

 

 

deviation - set the span of units from the closed

 

 

 

 

 

 

loop set point that will trigger a low alarm.

 

 

 

 

 

[`A;hi]

Alarm (1 to 4)

 

 

 

 

-1,999.000 to 9,999.000°F or units

300.0°F

Alarm Sides

[ A.hi]

High Set Point

 

 

 

 

-1,128.000 to 5,537.000°C

or units

(Setup Page) is

 

If Alarm Type (Setup Page, Alarm Menu) is set to:

 

 

 

150.0°C

not set to Low.

 

process - set the process value that will trigger a

 

 

 

 

 

 

high alarm.

 

 

 

 

 

 

 

 

deviation - set the span of units from the closed

 

 

 

 

 

 

loop set point that will trigger a high alarm.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[CUrr]

 

 

 

 

 

 

Note: To use the current sensing feature, Time Base (Setup Page, Output

[oPEr]

 

 

 

 

 

 

Current Menu

(menu appears if PM6 _ _ _-_ T _ _ A _ _)

 

Menu) must be set to 0.7 seconds or more.

 

 

 

 

 

 

 

 

 

 

 

[`C;hi]

Current

 

 

 

 

 

-1,999.000 to 9,999.000

50.0

Current Sides

[ C.hi]

High Set Point

 

 

 

 

 

 

(Setup Page) is

 

Set the current value that will trigger a high

 

 

 

 

set to High or

 

heater error state.

 

 

 

 

 

 

Both.

 

 

 

 

 

 

 

 

 

 

[`C;Lo]

Current

 

 

 

 

 

-1,999.000 to 9,999.000

0.0

Current Sides

[ C.Lo]

Low Set Point

 

 

 

 

 

 

(Setup Page) is

 

Set the current value that will trigger a low

 

 

 

 

set to Low or

 

heater error state.

 

 

 

 

 

 

Both.

 

 

 

 

 

 

 

 

 

 

[`CU;r]

Current

 

 

 

 

 

-1,999.000 to 9,999.000

0

always

[ CU.r]

Read

 

 

 

 

 

 

 

 

 

View the most recent current value monitored by

 

 

 

 

 

 

the current transformer.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[`C;Er]

Current

 

 

 

 

 

[nonE] None

None

always

[ C.Er]

Error

 

 

 

 

 

[Shrt] Shorted

 

 

 

View the cause of the most recent load fault.

 

 

[open] Open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[`h;Er]

Current

 

 

 

 

 

[nonE] None

None

always

[ h.Er]

Heater Error

 

 

 

 

[high] High

 

 

 

View the cause of the most recent load fault moni-

 

 

[Low] Low

 

 

 

tored by the current transformer.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[P;Sta]

 

 

 

 

 

 

* Some parameters in the Profile Status Menu can be changed for the

[oPEr]

 

 

 

 

 

 

currently running profile, but should only be changed by knowledgeable

Profile Status Menu (menu appears if PM6 R _ _ _-_ _ _ _ A _ _)

 

personnel and with caution. Changing parameters via the Profile Status

 

 

 

 

 

 

 

Menu will not change the stored profile but will have an immediate im-

 

 

 

 

 

 

 

pact on the profile that is running.

 

 

 

 

 

 

 

 

 

Changes made to profile parameters in the Profiling Pages will be

 

 

 

 

 

 

 

saved and will also have an immediate impact on the running profile.

 

 

 

 

 

 

 

 

 

 

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces.

If there is only one instance of a menu, no submenus will appear.

Watlow EZ-ZONE®PM Integrated Controller

31

Chapter 5 Operations Page