Display | Parameter name | Set- | Range | Default | Appears If |
| Description | tings |
|
|
|
|
|
|
|
|
|
[Loop] |
|
|
|
|
|
[oPEr] |
|
|
|
|
|
Loop Menu |
|
|
|
| |
|
|
|
|
|
|
[`r;En] | Loop |
| [``no] No | No | PM6 _ _ _ |
[ r;En] | Remote Enable |
| [`YES] Yes |
| ) _ _ A A A |
| Switch control to the remote set point. |
|
|
|
|
|
|
|
|
|
|
[`r;ty] | Loop |
| [AUto] Auto (closed loop) | Auto | Remote Enable |
[ r.ty] | Remote Set Point Type |
| [MAn] Manual (open loop) |
| is set to Yes. |
| Select how the remote set point will be deter- |
|
|
|
|
| mined. |
|
|
|
|
[`C;M] | Loop |
| [`off] Off | Auto | always |
[ C.M] | Control Mode |
| [AUto] Auto (closed loop) |
|
|
| Select the method that the controller will use to |
| [MAn] Manual (open loop) |
|
|
| control. |
|
|
| |
|
|
|
|
| |
|
|
|
|
|
|
[A;tSP] | Loop |
| 50.0 to 200.0% | 90.0 | Heat Algorithm |
[A.tSP} | Autotune Set Point |
|
|
| or Cool Algo- |
| Set the set point that the autotune will use, as a |
|
|
| rithm (Setup |
| percentage of the current set point. |
|
|
| Page) is set to |
|
|
|
|
| PID. |
|
|
|
|
|
|
[`AUt] | Loop |
| [``no] No | No | Heat Algorithm |
[ AUt] | Autotune Request |
| [`YES] Yes |
| or Cool Algo- |
| Start an autotune. While autotune is active, the |
|
|
| rithm (Setup |
| Home Page will display [Attn] [tUn1]. When |
|
|
| Page) is set to |
| the autotune is complete, the message will clear |
|
|
| PID. |
| automatically. |
|
|
|
|
|
|
|
|
|
|
[`C;SP] | Loop |
| Low Set Point to High Set Point | 75.0°F or | always |
[ C.SP] | Closed Loop Set Point |
| (Setup Page) | units |
|
| Set the set point that the controller will automati- |
|
| 24.0°C |
|
| cally control to. |
|
|
|
|
|
|
|
|
|
|
[`id;S] | Loop |
| Low Set Point to High Set Point | 75.0°F or | always |
[ id.S] | Idle Set Point |
| (Setup Page) | units |
|
| Set a closed loop set point that can be triggered by |
|
| 24.0°C |
|
| an event state. |
|
|
|
|
|
|
|
|
|
|
[`h;Pb] | Loop |
| 0.001 to 9,999.000°F or units | 25.0°F or | Heat Algorithm |
[ h.Pb] | Heat Proportional Band |
| units | (Setup Page) is | |
| Set the PID proportional band for the heat outputs. |
|
| 14.0°C | set to PID. |
|
|
|
|
|
|
[`h;hy] | Loop |
| 0.001 to 9,999.000°F or units | 3.0°F or | Heat Algorithm |
[ h.hy] | Heat Hysteresis |
| units | (Setup Page) is | |
| Set the control switching hysteresis for |
|
| 2.0°C | set to |
| trol. This determines how far into the “on” region |
|
|
|
|
| the process value needs to move before the output |
|
|
|
|
| turns on. |
|
|
|
|
|
|
|
|
|
|
[`C;Pb] | Loop |
| 0.001 to 9,999.000°F or units | 25.0°F or | Cool Algorithm |
[ C.Pb] | Cool Proportional Band |
| units | (Setup Page) is | |
| Set the PID proportional band for the cool outputs. |
|
| 14.0°C | set to PID. |
|
|
|
|
|
|
[`C;hy] | Loop |
| 0.001 to 9,999.000°F or units | 3.0°F or | Cool Algorithm |
[ C.hy] | Cool Hysteresis |
| units | (Setup Page) is | |
| Set the control switching hysteresis for |
|
| 2.0°C | set to |
| trol. This determines how far into the “on” region |
|
|
|
|
| the process value needs to move before the output |
|
|
|
|
| turns on. |
|
|
|
|
|
|
|
|
|
|
[``ti] | Loop |
| 0 to 9,999 seconds per repeat | 180.0 sec- | Heat Algorithm |
[ ti] | Time Integral |
|
| onds per | or Cool Algo- |
| Set the PID integral for the outputs. |
|
| repeat | rithm (Setup |
|
|
|
|
| Page) is set to |
|
|
|
|
| PID. |
|
|
|
|
|
|
[``td] | Loop |
| 0 to 9,999 seconds | 0.0 | Heat Algorithm |
[ td] | Time Derivative |
|
| seconds | or Cool Algo- |
| Set the PID derivative time for the outputs. |
|
|
| rithm (Setup |
|
|
|
|
| Page) is set to |
|
|
|
|
| PID. |
|
|
|
|
|
|
Note: Some values will be rounded off to fit in the
If there is only one instance of a menu, no submenus will appear.
Watlow | • 30 • | Chapter 5 Operations Page |