Ó

Warning:

Use National Electric (NEC) or other country-specific standard wiring and safety practices when wiring and connecting this controller to a power source and to electrical sensors or peripheral devices. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.

Low Power

Slot C

98 power fuse

99 power

CF

CD

CE

B5

D6

D5

12 to 40VÎ (dc)

20 to 28VÅ (ac)

20 to 28VÅ (ac) Semi Sig F47

47 to 63 Hz

10VA maximum power consumption PM6 _ (3 or 4) _ _-_ _ _ _ A _ _

Note:

Maximum wire size termination and torque rating:

0.0507 to 3.30 mm2 (30 to

12 AWG) single-wire termi- nation or two 1.31 mm2 (16 AWG)

0.8 Nm (7.0 lb.-in.) torque

Note:

Adjacent terminals may be labeled differently, depending on the model number.

High Power

Slot C

98 power fuse

99 power

CF

CD

CE

B5

D6

D5

85 to 264VÅ (ac)

100 to 240VÅ (ac) Semi Sig F47

47 to 63 Hz

10VA maximum power consumption PM6 _ (1 or 2) _ _-_ _ _ _ A _ _

Note:

To prevent damage to the controller, do not connect wires to unused terminals.

Note:

Maintain electrical isolation between analog input 1, digital input-outputs, switched dc/open collector outputs and process outputs to prevent ground loops.

Note:

Digital Input or Output 5

 

Slot C

 

Digital Input

 

 

98

 

update rate 10 Hz

 

 

 

dry contact or dc voltage

 

 

99

 

 

 

 

 

DC voltage

 

 

CF

 

 

 

 

 

• maximum input 36V at 3 mA

 

 

CD

 

minimum high state 3V @ 0.25 mA

 

 

 

 

 

CE

 

• maximum low state 2V

 

 

 

 

 

 

 

Dry contact

 

 

B5

common -

 

 

 

 

 

 

 

minimum open resistance 500 Ω

 

 

 

 

 

 

D6

 

maximum closed resistance 100 Ω

 

 

D5

input or output +

maximum short circuit 13 mA

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Output

update rate 10 Hz

output voltage 24V

current limit, Output 5, 24 mA maximum

capable of driving a 3-pole DIN-A-MITE

open-circuit voltage 22 to 32VÎ (dc)

PM6 _ (2 or 4) _ _-_ _ _ _ A _ _

The control output common terminal and the digital common terminal are referenced to different voltages and must remain isolated.

Digital Input or Output 6

 

Slot C

 

Digital Input

 

 

98

 

update rate 10 Hz

 

 

99

 

dry contact or dc voltage

 

 

 

 

 

 

 

DC voltage

 

 

CF

 

 

 

 

 

• maximum input 36V at 3 mA

 

 

 

 

 

 

CD

 

minimum high state 3V @ 0.25 mA

 

 

CE

 

• maximum low state 2V

 

 

 

 

 

 

 

Dry contact

 

 

B5

common -

 

 

 

 

D6

input or output +

minimum open resistance 500 Ω

 

 

 

 

 

maximum closed resistance 100 Ω

 

 

 

D5

 

maximum short circuit 13 mA

 

 

 

 

 

 

 

 

 

Digital Output

update rate 10 Hz

output voltage 24V

current limit, Output 6, 10 mA maximum

capable of driving a single-pole DIN-A-MITE

open-circuit voltage 22 to 32VÎ (dc)

PM6 _ (2 or 4) _ _-_ _ _ _ A _ _

Watlow EZ-ZONE®PM Integrated Controller

13