Indication | Description | Possible Cause(s) | Corrective Action |
|
|
|
|
[Li;h1] Limit High | Sensor input above high limit | • Temperature is greater than limit set | • Check cause of over temperature |
[Li;h2] | set point | point |
|
|
| • Limit outputs latch and require reset | • Clear limit |
|
| • Incorrect alarm set point | • Establish correct limit set point |
|
|
|
|
[LP;o1] | Open Loop Detect is active | • Setting of Open Loop Detect Time | • Set correct Open Loop Detect Time for |
Loop Open Error | and the process value did | incorrect | application |
| not deviate by a | • Setting of Open Loop Detect Devia- | • Set correct Open Loop Deviation value |
| ed value in a user specified | tion incorrect | for application |
| period. | • Thermal loop is open | • Determine cause of open thermal loop: |
|
| ||
|
|
| misplaced sensors, load failure, loss of |
|
|
| power to load, etc. |
|
| • Open Loop Detect function not re- | • Deactivate Open Loop Detect feature |
|
| quired but activated |
|
|
|
|
|
[LP;r1] | Open Loop Detect is active | • Setting of Open Loop Detect Time | • Set correct Open Loop Detect Time for |
Loop Reversed Error | and the process value is | incorrect | application |
| headed in the wrong direc- | • Setting of Open Loop Detect Devia- | • Set correct Open Loop Deviation value |
| tion when the output is | tion incorrect | for application |
| activated based on devia- | • Output programmed for incorrect | • Set output function correctly |
| tion value and | ||
| function |
| |
| value. |
| |
| • Thermocouple sensor wired in reverse | • Wire thermocouple correctly, (red wire | |
|
| ||
|
| polarity | is negative) |
|
|
|
|
[`rP1] Ramping 1 | Controller is ramping to new | • Ramping feature is activated | • Disable ramping feature if not re- |
| set point |
| quired |
|
|
|
|
[tUN1] Autotuning 1 | Controller is autotuning the | • User started the autotune function | • Wait until autotune completes or dis- |
| control loop |
| able autotune feature |
|
| • Digital input is set to start autotune | • Set digital input to function other |
|
|
| than autotune, if desired |
|
|
|
|
No heat/cool action | Output does not activate load | • Output function is incorrectly set | • Set output function correctly |
|
| • Control mode is incorrectly set | • Set control mode appropriately (Open |
|
|
| vs Closed Loop) |
|
| • Output is incorrectly wired | • Correct output wiring |
|
| • Load, power or fuse is open | • Correct fault in system |
|
| • Control set point is incorrect | • Set control set point in appropriate |
|
|
| control mode and check source of set |
|
|
| point: remote, idle, profile, closed loop, |
|
|
| open loop |
|
| • Incorrect controller model for applica- | • Obtain correct controller model for ap- |
|
| tion | plication |
|
|
|
|
No Display | No display indication or LED | • Power to controller is off | • Turn on power |
| illumination | • Fuse open | • Replace fuse |
|
| • Breaker tripped | • Reset breaker |
|
| • Safety interlock switch open | • Close interlock switch |
|
| • Separate system limit control acti- | • Reset limit |
|
| vated |
|
|
| • Wiring error | • Correct wiring issue |
|
| • Incorrect voltage to controller | • Apply correct voltage, check part |
|
|
| number |
|
|
|
|
No Serial Communi- | Cannot establish serial com- | • Address parameter incorrect | • Set unique addresses on network |
cation | munications with the con- | • Incorrect protocol selected | • Match protocol between devices |
| troller | • Baud rate incorrect | • Match baud rate between devices |
|
| ||
|
| • Parity incorrect | • Match parity between devices |
|
| • Wiring error | • Correct wiring issue |
|
| • | • Check settings or replace converter |
|
| • Incorrect computer or PLC communi- | • Set correct communication port |
|
| cations port |
|
|
| • Incorrect software setup | • Correct software setup to match con- |
|
|
| troller |
|
| • Termination resistor may be required | • Place 120 Ω resistor across |
|
|
| on last controller |
|
|
|
|