Solid-State Relay

0.5 A @ 24 to 264VÅ (ac) maximum, opto-isolated, without con- tact suppression; maximum off-state leakage current: 105 micro- amperes

Electromechanical Relay, Form A

5 A, 24 to 240VÅ (ac) or 30VÎ (dc) maximum, resistive load, 100,000 cycles at rated load, 125 VA pilot duty

Requires a minimum load of 20 mA @ 24V

Electromechanical Relay, Form C

5 A, 24 to 240VÅ (ac) or 30VÎ (dc) maximum, resistive load, 100,000 cycles at rated load, 125 VA pilot duty

Requires a minimum load of 20 mA @ 24V

No-arc Relay Form A

15 A, 85 to 264VÅ (ac), no VÎ (dc), resistive load, 2 million cycles at rated load (preliminary), maximum off-state leakage current: 2 mA

Process

Universal process/Retransmit, outputs range selectable, 0 to 10 VÎ (dc) into minimum 1,000 Ω load, 0 to 20 mA into maximum 800 Ω load

Operator Interface

Dual 4-digit, 7-segment LED displays

Advance, infinity, up and down keys plus an EZ Key program- mable function key

Typical display update rate 1Hz

Agency approved to IP66/NEMA 4X

Dimensions

Size

Behind

Width

Height

Display Height

 

Panel

 

 

 

 

(max.)

 

 

 

1/16

101.6 mm

53.3 mm

53.3 mm

up: 10.80 mm (0.425 in)

 

(4.00 in)

(2.10 in)

(2.10 in)

low: 6.98 mm (0.275 in)

 

 

 

 

 

Weight

Controller: 200 g (7.1 oz.)

User manual: 167.26 g (5.9 oz)

Modbus® is a trademark of AEG Schneider Automation Inc.

EtherNet/IP™ is a trademark of ControlNet International Ltd. used under license by Open DeviceNet Vendor Association, Inc. (ODVA).

UL® is a registered trademark of Underwriters Laboratories Inc.

DeviceNet™ is a trademark of Open DeviceNet Vendors Associatlon.

Note: These specifications are subject to change without prior notice.