•0.5 A @ 24 to 264VÅ (ac) maximum,
Electromechanical Relay, Form A
•5 A, 24 to 240VÅ (ac) or 30VÎ (dc) maximum, resistive load, 100,000 cycles at rated load, 125 VA pilot duty
•Requires a minimum load of 20 mA @ 24V
Electromechanical Relay, Form C
•5 A, 24 to 240VÅ (ac) or 30VÎ (dc) maximum, resistive load, 100,000 cycles at rated load, 125 VA pilot duty
•Requires a minimum load of 20 mA @ 24V
•15 A, 85 to 264VÅ (ac), no VÎ (dc), resistive load, 2 million cycles at rated load (preliminary), maximum
Process
•Universal process/Retransmit, outputs range selectable, 0 to 10 VÎ (dc) into minimum 1,000 Ω load, 0 to 20 mA into maximum 800 Ω load
Operator Interface•Dual
•Advance, infinity, up and down keys plus an EZ Key program- mable function key
•Typical display update rate 1Hz
•Agency approved to IP66/NEMA 4X
DimensionsSize | Behind | Width | Height | Display Height |
| Panel |
|
|
|
| (max.) |
|
|
|
1/16 | 101.6 mm | 53.3 mm | 53.3 mm | up: 10.80 mm (0.425 in) |
| (4.00 in) | (2.10 in) | (2.10 in) | low: 6.98 mm (0.275 in) |
|
|
|
|
|
•Controller: 200 g (7.1 oz.)
•User manual: 167.26 g (5.9 oz)
Modbus® is a trademark of AEG Schneider Automation Inc.
EtherNet/IP™ is a trademark of ControlNet International Ltd. used under license by Open DeviceNet Vendor Association, Inc. (ODVA).
UL® is a registered trademark of Underwriters Laboratories Inc.
DeviceNet™ is a trademark of Open DeviceNet Vendors Associatlon.
Note: These specifications are subject to change without prior notice.Watlow | • 70 • | Appendix |