EZ-ZONE®PM Integrated Model 1/16 DIN with a Limit — Input/Output

(no communications options 2 to 3)

Universal Sensor Input, Configuration Communications,

Red/Green 7-Segment Display

Input

Functions

input sensor

none, limit reset, idle set point, tune,

alarm reset, silence alarm, manual/auto mode, control outputs off, lock keypad, force alarm, TRU-TUNE+®disable loop & alarms off, profile disable, profile hold/resume, profile start, profile start/stop, restore user settings

Network

remote user interface, personal computer, programmable logic controller, human- machine interface

input sensor

Analog Input 1 thermocouple, RTD, process (V, mV, mA, 1k po- tentiometer)

Digital Input (or Output) 5

(optional) none, switch, volts dc

Digital Input (or Output) 6 (optional) none, switch, volts dc

EZ Key programmable event

EIA 485 Communications

Standard Bus, Modbus RTU (optional)

Analog Input 2 thermocouple, RTD, process (V, mV, mA, 1k po- tentiometer)

PID

Controller

Board

Slot A

ramp-soak with 4 files (optional)

Supervisory

&

Power

Board

Slot C

Limit

Controller

Board

(optional)

Slot B

Output 1 none, switched dc/open collector, form C mechanical (5 A) or solid-state (0.5 A) relay, process (V, mA)

Output 2 none, switched dc, no-arc power control (15 A), form A mechanical (5 A) or solid-state (0.5 A) relay

Digital Output (or Input) 5 (optional) none, switched dc

Digital Output (or Input) 6 (optional) none, switched dc

Output 3 none, switched dc/open collector, form C mechanical (5 A) or solid-state (0.5 A) relay, process (V, mA)

Output 4

form A mechanical (5 A) relay

Output

Functions

off, heat, cool, duplex, alarm, retransmit, event

off, heat, cool, alarm, event

off, heat, cool, alarm, event

off, heat, cool, alarm, event

off, heat, cool, duplex, alarm, retransmit, event, limit

limit

Integrated PID and Limit Controller

Reduces wiring time and termination complexity compared to connecting separate products

Reduces panel space

Reduces installation costs

Increases dependability with backup control sensor operation

Increases user and equipment safety for over-under temperature conditions

Watlow EZ-ZONE®PM Integrated Controller

6

Chapter 1 Overview