Ó

Output 1 Switched DC/Open Collector

Warning:

Use National Electric (NEC) or other country-specific standard wiring and safety practices when wiring and connecting this controller to a power source and to electrical sensors or peripheral devices. Failure to do so may result in damage to equipment and property, and/or injury or loss of life.

Note:

Maximum wire size termination and torque rating:

0.0507 to 3.30 mm2 (30 to

12 AWG) single-wire termi- nation or two 1.31 mm2 (16 AWG)

0.8 Nm (7.0 lb.-in.) torque

Note:

Adjacent terminals may be labeled differently, depending on the model number.

Slot A

common X1

dc - (open collector)

W1

dc +

Y1

L2

K2

T1

S1

R1

Switched DC

30 mA dc maximum supply current

short circuit limited to <50 mA

22 to 32VÎ (dc) open circuit voltage

Use dc- and dc+ to drive exter- nal solid-state relay.

DIN-A-MITE compatible

single-pole: up to 4 in parallel or 4 in series

2-pole: up to 2 in parallel or 2 in series

3-pole: up to 2 in series

Open Collector

100 mA maximum output cur- rent sink

30VÎ (dc) maximum supply voltage

Any switched dc output can use the common terminal.

Use an external power supply to control a dc load, with the load positive to the positive of the power supply, the load negative to the open collector and common to the power sup- ply negative.

See Quencharc note.

PM6 _ _ C _-_ _ _ _ A _ _

Switched DC

-

dc-

W1

Load

dc+

+

 

Y1

Internal

Circuitry

Power

 

 

Open

 

 

Collector

Supply

 

+

-

X1 common

 

 

 

 

W1

dc-

+

 

 

 

Load

 

 

dc+

 

 

 

 

 

 

Internal

 

 

 

Circuitry

Note:

Output 1 Mechanical Relay, Form C

To prevent damage to the controller, do not connect

Slot A

normally open L1

• 5 A at 240VÅ (ac) or 30VÎ (dc)

wires to unused terminals.

Note:

common

normally closed

K1

J1

 

maximum resistive load

20 mA at 24V minimum load

125 VA pilot duty at 120/240VÅ

 

Å

L1

Mechanical

Relay

normally open

Maintain electrical isolation between analog input 1, digital input-outputs, switched dc/open collector outputs and process outputs to prevent ground loops.

Note:

L2

K2

T1

S1

R1

 

(ac), 25 VA at 24V (ac)

100,000 cycles at rated load

• Output does not supply power.

for use with ac or dc

See Quencharc note. PM6 _ _ E _-_ _ _ _ A _ _

K1 common

J1 normally

closed Internal Circuitry

The control output common terminal and the digital com-

Output 1 Universal Process

mon terminal are referenced to different voltages and must remain isolated.

Quencharc Note:

Switching pilot duty inductive loads (relay coils, solenoids, etc.) with the mechanical relay, solid state relay or open collector output options requires use of an R.C. sup-

Slot A

volts or current - F1

volts +

G1

current +

H1

L2

K2

T1

S1

R1

0 to 20 mA into 800 Ω maxi- mum load

0 to 10VÎ (dc) into voltage 1 kΩ minimum load

scalable

output supplies power

cannot use voltage and current outputs at same time

Output may be used as re- transmit or control.

PM6 _ _ F _-_ _ _ _ A _ _

pressor.

Note: If output 1 is a universal process output, output 2 cannot function as a variable-time-base output.

Watlow EZ-ZONE®PM Integrated Controller

17