Dis-

 

Parameter Name

 

Set-

Range

Default

Appears If

play

 

Description

 

tings

 

 

 

 

[otpt]

 

[```1]

[```2]

[```3]

[```4]

 

 

 

[`Set]

 

[otpt]

[otPt]

[otpt]

[otpt]

 

 

 

Output Menu

Output 1

Output 2

Output 3

Output 4

(check model number for output information)

 

 

 

 

 

 

 

 

 

[`o;ty]

Output (1 or 3)

 

 

 

[uoLt] Volts

 

Volts

a process output (PM6 _

[ o.ty]

Type

 

 

 

 

[`MA] Milliamps

 

_ F _-_ _ _ _ A _ _ or PM6

 

Select whether the process output will op-

 

 

 

 

_ _ _-_ _ F _ A _ _)

 

erate in volts or milliamps.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[``Fn]

Output (1 or 3)

 

 

 

[`oFF] Off

 

Heat (output 1)

a process output (PM6 _

[ Fn]

Function

 

 

 

 

[hEAt] Heat

 

Off (output 2)

_ F _-_ _ _ _ A _ _ or PM6

 

Select what function will drive this output.

 

[CooL] Cool

 

 

_ _ _-_ _ F _ A _ _)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[dUPL] Duplex

 

 

 

 

 

 

 

 

 

[ALM] Alarm

 

 

 

 

 

 

 

 

 

[`Ent] Event

 

 

 

 

 

 

 

 

 

[rMt] Retransmit

 

 

 

 

 

 

 

 

 

 

[`r;Sr]

Output (1 or 3)

 

 

 

[``Ai] Analog Input

Analog Input

a process output (PM6

[ r.Sr]

Retransmit Source

 

 

 

[StPt] Set Point

 

_ _ F _-_ _ _ _ A _ _ or

 

Select the value that will be retransmitted.

 

[CUrr] Current

 

 

PM6 _ _ _-_ _ F _ A _ _)

 

 

 

 

 

 

 

 

and Function is set to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Retransmit.

 

 

 

 

 

 

 

 

 

[``Fi]

Output (1 or 3)

 

 

 

1 to 4

 

1

a process output (PM6 _

[ Fi]

Function Instance

 

 

 

 

 

 

_ F _-_ _ _ _ A _ _ or PM6

 

Select which source instance will drive the

 

 

 

 

_ _ _-_ _ F _ A _ _) and

 

output.

 

 

 

 

 

 

 

there is more than one

 

 

 

 

 

 

 

 

 

instance of the Function

 

 

 

 

 

 

 

 

 

selection.

 

 

 

 

 

 

 

 

 

[`S;Lo]

Output (1 or 3)

 

 

 

0.00 to 20.00

 

0.00

a process output (PM6 _

[ S.Lo]

Scale Low

 

 

 

 

 

 

 

_ F _-_ _ _ _ A _ _ or PM6

 

Set the minimum value of the process out-

 

 

 

 

_ _ _-_ _ F _ A _ _)

 

put range in electrical units.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[`S;hi]

Output (1 or 3)

 

 

 

0.00 to 20.00

 

10.00

a process output (PM6 _

[ S.hi]

Scale High

 

 

 

 

 

 

_ F _-_ _ _ _ A _ _ or PM6

 

Set the maximum value of the process out-

 

 

 

 

_ _ _-_ _ F _ A _ _)

 

put range in electrical units.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[`r;Lo]

Output (1 or 3)

 

 

 

-1,999.000 to 9,999.000°F or

0.0°F or units

a process output (PM6

[ r.Lo]

Range Low

 

 

 

units

 

-18°C

_ _ F _-_ _ _ _ A _ _ or

 

Set the minimum value of the retransmit

 

 

-1,128.000 to 5,537.000°C

 

PM6 _ _ _-_ _ F _ A _ _)

 

value range in process units. When the

 

 

 

 

 

and Function is set to

 

retransmit source is at this value, the

 

 

 

 

 

Retransmit.

 

retransmit output will be at its Scale Low

 

 

 

 

 

 

value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[`r;hi]

Output (1 or 3)

 

 

 

-1,999.000 to 9,999.000°F or

9,999.0°F or

a process output (PM6

[ r.hi]

Range High

 

 

 

units

 

units

_ _ F _-_ _ _ _ A _ _ or

 

Set the maximum value of the retransmit

 

-1,128.000 to 5,537.000°C

5,537.0°C

PM6 _ _ _-_ _ F _ A _ _)

 

value range in process units. When the

 

 

 

 

 

and Function is set to

 

retransmit source is at this value, the re-

 

 

 

 

 

Retransmit.

 

transmit output will be at its Scale High

 

 

 

 

 

 

 

value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[`o;Lo]

Output (1 or 3)

 

 

 

0.0 to 100.0%

 

0.0

a process output (PM6 _ _

[ o.Lo]

Low Power Scale

 

 

 

 

 

 

F _-_ _ _ _ A _ _ or PM6

 

Set the minimum value of the output

 

 

 

 

 

_ _ _-_ _ F _ A _ _) and

 

range.

 

 

 

 

 

 

 

Function is set to Heat

 

 

 

 

 

 

 

 

 

or Cool.

 

 

 

 

 

 

 

 

 

[`o;hi]

Output (1 or 3)

 

 

 

0.0 to 100.0%

 

100.0

a process output (PM6 _ _

[ o.hi]

High Power Scale

 

 

 

 

 

 

F _-_ _ _ _ A _ _ or PM6

 

Set the maximum value of the output

 

 

 

 

 

_ _ _-_ _ F _ A _ _) and

 

range.

 

 

 

 

 

 

 

Function is set to Heat

 

 

 

 

 

 

 

 

 

or Cool.

 

 

 

 

 

 

 

 

[`o;CA]

Output (1 or 3)

 

 

 

-1,999.000 to 9,999.000°F or

0.0°F or units

a process output (PM6 _ _

[ o.CA]

Calibration Offset

 

 

 

units

 

0.0°C

F _-_ _ _ _ A _ _ or PM6

 

Set an offset value for a process output.

 

 

-1,110.555 to 5,555.000°C

 

_ _ _-_ _ F _ A _ _)

 

 

 

 

 

 

 

 

 

 

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces. If there is only one instance of a menu, no submenus will appear.

Watlow EZ-ZONE®PM Integrated Controller

39

Chapter 6 Setup Page