Output 2 Solid-state Relay, Form A
Warning:
Use National Electric (NEC) or other
Slot A
L1
K1
J1
normally open L2
common K2
T1
S1
R1
•0.5 A at 20 to 264VÅ (ac) maxi- mum resistive load
•20 VA 120/240VÅ (ac) pilot duty
•
•maximum off state leakage of 105 microamperes
•Output does not supply power.
•Do not use on dc loads.
See Quencharc note.
PM6 _ _ _
normally L2 open
K2 common
Internal Circuitry
Output 3 Switched DC/Open Collector
Note:
Maximum wire size termination and torque rating:
•0.0507 to 3.30 mm2 (30 to
12 AWG)
•0.8 Nm (7.0
Note:
Adjacent terminals may be labeled differently, depending on the model number.
Note:
To prevent damage to the controller, do not connect wires to unused terminals.
Note:
Maintain electrical isolation between analog input 1, digital
Slot B
common X3
dc - (open collector) W3
dc +
Y3
L4
K4
T2
S2
R2
Switched DC
•30 mA dc maximum supply current
•short circuit limited to <50 mA
•22 to 32VÎ (dc) open circuit voltage
•Use dc- and dc+ to drive exter- nal
•
•
•
•
Open Collector
•100 mA maximum output cur- rent sink
•30VÎ (dc) maximum supply voltage
•Any switched dc output can use the common terminal.
•Use an external power supply to control a dc load, with the load positive to the positive of the power supply, the load negative to the open collector and common to the power sup- ply negative.
See Quencharc note.
PM6 _ _ _
Switched DC
- | dc- | |
W3 | ||
Load | ||
dc+ | ||
+ | ||
| Y3 |
Internal
Circuitry
Power |
|
| Open |
|
| Collector | |
Supply |
| ||
+ | - | X3 common | |
|
| ||
|
| W3 | dc- |
+ |
|
|
|
Load |
|
| dc+ |
|
|
| |
|
|
| Internal |
|
|
| Circuitry |
Note:
The control output common
Output 3 Mechanical Relay, Form C
terminal and the digital common terminal are referenced
Slot B
normally open L3
• 5 A at 240VÅ (ac) or 30VÎ (dc) |
to different voltages and must remain isolated.
Quencharc Note:
common
normally closed
K3
J3
L4
| maximum resistive load |
• | 20 mA at 24V minimum load |
• | 125 VA pilot duty at 120/240VÅ |
| (ac), 25 VA at 24VÅ (ac) |
L3
Mechanical
Relay
normally open
Switching pilot duty inductive loads (relay coils, solenoids, etc.) with the mechanical relay, solid state relay or open collector output options requires use of an R.C. sup- pressor.
K4
T2
S2
R2
• | 100,000 cycles at rated load |
• Output does not supply power. | |
• | for use with ac or dc |
See Quencharc note. PM6 _ _ _
K3 common
J3 normally
closed Internal Circuitry
Watlow | • 19 • | Chapter 2 Install and Wire |