Dis-

Parameter Name

Set-

Range

Default

Appears If

play

Description

tings

 

 

 

[P;typ]

Global

 

 

[StPt] Set Point

Set Point

the controller includes

[P.tyP]

Profile Type

 

 

[`Pro] Process

 

profiling (PM6 R _ _ _-_

 

Set the profile startup to be based on a set

 

 

 

_ _ _ A _ _).

 

point or a process value.

 

 

 

 

 

 

 

 

 

 

 

[`GSE]

Global

 

 

[`oFF] Off

Off

the controller includes

[ gSE]

Guaranteed Soak Enable

 

[``on] On

 

profiling (PM6 R _ _ _-_

 

Enables the guaranteed soak deviation

 

 

 

_ _ _ A _ _).

 

function in profiles.

 

 

 

 

 

 

 

 

 

 

 

 

[`GSd]

Global

 

 

0.0 to 9,999.000°F or units

10.0°F or units

the controller includes

[ gSd]

Guaranteed Soak Deviation

 

0.0 to 5,555.000°C

6.0°C

profiling (PM6 R _ _ _-_

 

Set the value of the deviation band that

 

 

 

_ _ _ A _ _).

 

will be used in all profile step types. The

 

 

 

 

 

process value must enter the deviation

 

 

 

 

 

band before the step can proceed.

 

 

 

 

 

 

 

 

 

 

 

[CoM]

 

[```1]

[```2]

 

 

[`SEt]

 

[CoM]

[CoM]

 

 

Communications Menu

Communications 1

Communications 2

 

 

 

 

 

 

 

 

 

[PCoL]

Communications 1

 

 

[`Std] Standard Bus

Modbus

the controller includes

[PCoL]

Protocol

 

 

[Mod] Modbus RTU

 

Modbus RTU (PM6 _ _

 

Set the protocol of this controller to the

 

 

 

_ _-1_ _ _ A _ _).

 

protocol that this network is using.

 

 

 

 

 

 

 

 

 

 

 

[`Ad;S]

Communications 1

 

 

1 to 16

1

Protocol is set to Stan-

[ Ad.S]

Address Standard Bus

 

 

 

dardbus

 

Set the network address of this controller.

 

 

 

Range depends on the

 

Each device on the network must have a

 

 

 

model.

 

unique address.

 

 

 

 

 

 

The Zone Display on the front panel will

 

 

 

 

 

display this number.

 

 

 

 

 

 

 

 

 

 

 

[Ad;M]

Communications (1 or 2)

 

1 to 247

1

Protocol is set to Modbus

[Ad.M]

Address Modbus

 

 

 

 

Range depends on the

 

Set the network address of this controller.

 

 

 

model.

 

Each device on the network must have a

 

 

 

 

 

unique address.

 

 

 

 

 

 

 

 

 

 

 

[bAUd]

Communications (1 or 2)

 

9,600

9,600

Protocol is set to Modbus.

[bAUd]

Baud Rate Modbus

 

 

19,200

 

Range depends on the

 

Set the speed of this controller's commu-

 

38,400

 

model.

 

nications to match the speed of the serial

 

 

 

 

 

network.

 

 

 

 

 

 

 

 

 

 

 

 

[`PAr]

Communications

 

 

[none] None

None

Protocol is set to Modbus.

[ PAr]

Parity Modbus (1 or 2)

 

[EuEn] Even

 

Range depends on the

 

Set the parity of this controller to match

 

[`odd] Odd

 

model.

 

the parity of the serial network.

 

 

 

 

[M;hL]

Communications (1 or 2)

 

[Lohi] Low-High

Low-High

Protocol is set to Modbus.

[M.hL]

Modbus Word Order

 

[hiLo] High-Low

 

 

 

Select the word order of the two 16-bit

 

 

 

 

 

words in the floating-point values.

 

 

 

 

 

 

 

 

 

 

 

[iP;M]

Communications 2

 

 

[dhCP] DHCP

 

the controller includes

[iP.M]

IP Address Mode

 

 

[F;Add] Fixed Address

 

EtherNet/IP (PM6 _ _ _

 

Select DHCP to let a DHCP server assign

 

 

 

_-3AA_ A _ _).

 

an address to this controller.

 

 

 

 

 

 

 

 

 

 

 

[iP;F1]

Communications 2

 

 

0 to 255

169

IP Address Mode is set

[ip.F1]

IP Fixed Address Part 1

 

 

 

to Fixed

 

Set the IP address of this controller. Each

 

 

 

 

 

device on the network must have a unique

 

 

 

 

 

address.

 

 

 

 

 

 

 

 

 

 

 

 

[iP;F2]

Communications 2

 

 

0 to 255

254

IP Address Mode is set

[ip.F2]

IP Fixed Address Part 2

 

 

 

to Fixed

 

Set the IP address of this controller. Each

 

 

 

 

 

device on the network must have a unique

 

 

 

 

 

address.

 

 

 

 

 

 

 

 

 

 

 

 

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces. If there is only one instance of a menu, no submenus will appear.

Watlow EZ-ZONE®PM Integrated Controller

43

Chapter 6 Setup Page