To go to the Setup Page from the Home Page, press both the Up ¿ and Down ¯ keys for six seconds. [``Ai] will appear in the upper display and [`Set] will appear in the lower display.
•Press the Up ¿ or Down ¯ key to move through the menus.
•Press the Advance Key ‰ to move to a submenu.
•Press the Up ¿ or Down ¯ key to move through the submenus.
•Press the Advance Key ‰ to move through the pa- rameters of the menu or submenu.
•Press the Infinity Key ˆ to move backwards through the levels: parameter to submenu; sub- menu to menu; menu to Home Page.
•Press and hold the Infinity Key ˆ for two seconds to return to the Home Page.
Note: Avoid continuous writes within loops. Excessive writes to EEPROM will cause premature EEPROM failure. The EEPROM is rated for 1,000,000 writes.
Dis- | Parameter Name |
| Set- |
| Range | Default | Appears If | |
play | Description |
| tings |
|
|
|
|
|
[``Ai] | [```1] | [```2] |
|
|
|
|
| |
[`Set] | [``Ai] | [``Ai] |
|
|
|
| ||
Analog Input Menu Analog Input 1 or | Analog Input 2 |
| (input 2 appears if PM6 _ _ _ | |||||
|
|
|
|
|
|
|
|
|
[`Sen] | Input (1 or 2) |
|
| [`oFF] Off |
|
| Thermocouple | always |
[ SEn] | Sensor Type |
|
| [``tC] Thermocouple |
|
| ||
| Set the analog sensor type to match the |
| [`mu] Millivolts |
|
| |||
| device wired to this input. |
|
|
|
| |||
|
|
| [uolT] Volts dc |
|
| |||
|
|
|
|
|
| |||
| Note: There is no |
|
| [`MA] Milliamps dc |
|
| ||
| process inputs. |
|
| [r0;1H] RTD 100 Ω |
|
| ||
|
|
|
| [r1;0H] RTD 1,000 Ω |
|
| ||
|
|
|
| [`Pot] Potentiometer 1 kΩ |
|
| ||
|
|
|
|
|
|
|
|
|
[`Lin] | Input (1 or 2) |
|
| [```b] B |
| [```H] K | J | Sensor Type is set to |
[ Lin] | Linearization |
|
| [```C] C |
| [```n] N |
| Thermocouple. |
| Set the linearization to match the thermo- |
| [```d] D |
| [```r] R |
|
| |
| couple wired to this input. |
|
|
|
|
| ||
|
|
| [```E] E |
| [```S] S |
|
| |
|
|
|
|
|
|
| ||
|
|
|
| [```F] F |
| [```t] T |
|
|
|
|
|
| [```J] J |
|
|
|
|
|
|
|
|
|
|
|
|
|
[`Rt;L] | Input (1 or 2) |
|
| [```2] 2 |
|
| 2 | Sensor Type is set to |
[ rt.L] | RTD Leads |
|
| [```3] 3 |
|
|
| RTD 100 Ω or RTD |
| Set to match the number of leads on the |
|
|
|
|
| 1,000 Ω. | |
| RTD wired to this input. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
[`S;Lo] | Input (1 or 2) |
|
| 0.0 | Sensor Type is set to Mil- | |||
[ S.Lo] | Scale Low |
|
|
|
|
|
| livolts, Volts, Milliamps |
| Set the low scale for process inputs. This |
|
|
|
|
| or Potentiometer 1 kΩ. | |
| value, in millivolts, volts or milliamps, will |
|
|
|
|
|
| |
| correspond to the Range Low displayed by |
|
|
|
|
|
| |
| the controller. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
[`S;hi] | Input (1 or 2) |
|
| 20.0 | Sensor Type is set to Mil- | |||
[ S.hi] | Scale High |
|
|
|
|
|
| livolts, Volts, Milliamps |
| Set the high scale for process inputs. This |
|
|
|
|
| or Potentiometer 1 kΩ. | |
| value, in millivolts, volts or milliamps, will |
|
|
|
|
|
| |
| correspond to the Range High displayed by |
|
|
|
|
|
| |
| the controller. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
[`r;Lo] | Input (1 or 2) |
|
| 0.0 | Sensor Type is set to Mil- | |||
[ r.Lo] | Range Low |
|
|
|
|
|
| livolts, Volts, Milliamps |
| Set the low range for the displayed process |
|
|
|
|
| or Potentiometer 1 kΩ. | |
| input units. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
[`r;hi] | Input (1 or 2) |
|
| 9,999 | Sensor Type is set to Mil- | |||
[ r.hi] | Range High |
|
|
|
|
|
| livolts, Volts, Milliamps |
| Set the high range for the displayed pro- |
|
|
|
|
| or Potentiometer 1 kΩ. | |
| cess input units. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
[`P;EE] | Input (1 or 2) |
|
| [`off] Off |
|
| Off | Sensor Type is set to Mil- |
[ P.EE] | Process Error Enable |
|
| [Low] Low |
| livolts, Volts, Milliamps | ||
| Turn the Process Error Low feature on or |
|
|
|
|
| or Potentiometer 1 kΩ. | |
| off. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note: Some values will be rounded off to fit in the
Watlow | • 34 • | Chapter 6 Setup Page |