To go to the Setup Page from the Home Page, press both the Up ¿ and Down ¯ keys for six seconds. [``Ai] will appear in the upper display and [`Set] will appear in the lower display.

Press the Up ¿ or Down ¯ key to move through the menus.

Press the Advance Key to move to a submenu.

Press the Up ¿ or Down ¯ key to move through the submenus.

Press the Advance Key to move through the pa- rameters of the menu or submenu.

Press the Infinity Key ˆ to move backwards through the levels: parameter to submenu; sub- menu to menu; menu to Home Page.

Press and hold the Infinity Key ˆ for two seconds to return to the Home Page.

Note: Avoid continuous writes within loops. Excessive writes to EEPROM will cause premature EEPROM failure. The EEPROM is rated for 1,000,000 writes.

Dis-

Parameter Name

 

Set-

 

Range

Default

Appears If

play

Description

 

tings

 

 

 

 

 

[``Ai]

[```1]

[```2]

 

 

 

 

 

[`Set]

[``Ai]

[``Ai]

 

 

 

 

Analog Input Menu Analog Input 1 or

Analog Input 2

 

(input 2 appears if PM6 _ _ _ _-_ [R, T or L] _ _ A _ _)

 

 

 

 

 

 

 

 

 

[`Sen]

Input (1 or 2)

 

 

[`oFF] Off

 

 

Thermocouple

always

[ SEn]

Sensor Type

 

 

[``tC] Thermocouple

 

 

 

Set the analog sensor type to match the

 

[`mu] Millivolts

 

 

 

device wired to this input.

 

 

 

 

 

 

 

[uolT] Volts dc

 

 

 

 

 

 

 

 

 

Note: There is no open-sensor detection for

 

 

[`MA] Milliamps dc

 

 

 

process inputs.

 

 

[r0;1H] RTD 100 Ω

 

 

 

 

 

 

[r1;0H] RTD 1,000 Ω

 

 

 

 

 

 

[`Pot] Potentiometer 1 kΩ

 

 

 

 

 

 

 

 

 

 

 

[`Lin]

Input (1 or 2)

 

 

[```b] B

 

[```H] K

J

Sensor Type is set to

[ Lin]

Linearization

 

 

[```C] C

 

[```n] N

 

Thermocouple.

 

Set the linearization to match the thermo-

 

[```d] D

 

[```r] R

 

 

 

couple wired to this input.

 

 

 

 

 

 

 

 

[```E] E

 

[```S] S

 

 

 

 

 

 

 

 

 

 

 

 

 

[```F] F

 

[```t] T

 

 

 

 

 

 

[```J] J

 

 

 

 

 

 

 

 

 

 

 

 

 

[`Rt;L]

Input (1 or 2)

 

 

[```2] 2

 

 

2

Sensor Type is set to

[ rt.L]

RTD Leads

 

 

[```3] 3

 

 

 

RTD 100 Ω or RTD

 

Set to match the number of leads on the

 

 

 

 

 

1,000 Ω.

 

RTD wired to this input.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[`S;Lo]

Input (1 or 2)

 

 

-100.0 to 1,000.0

0.0

Sensor Type is set to Mil-

[ S.Lo]

Scale Low

 

 

 

 

 

 

livolts, Volts, Milliamps

 

Set the low scale for process inputs. This

 

 

 

 

 

or Potentiometer 1 kΩ.

 

value, in millivolts, volts or milliamps, will

 

 

 

 

 

 

 

correspond to the Range Low displayed by

 

 

 

 

 

 

 

the controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[`S;hi]

Input (1 or 2)

 

 

-100.0 to 1,000.0

20.0

Sensor Type is set to Mil-

[ S.hi]

Scale High

 

 

 

 

 

 

livolts, Volts, Milliamps

 

Set the high scale for process inputs. This

 

 

 

 

 

or Potentiometer 1 kΩ.

 

value, in millivolts, volts or milliamps, will

 

 

 

 

 

 

 

correspond to the Range High displayed by

 

 

 

 

 

 

 

the controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[`r;Lo]

Input (1 or 2)

 

 

-1,999.000 to 9,999.000

0.0

Sensor Type is set to Mil-

[ r.Lo]

Range Low

 

 

 

 

 

 

livolts, Volts, Milliamps

 

Set the low range for the displayed process

 

 

 

 

 

or Potentiometer 1 kΩ.

 

input units.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[`r;hi]

Input (1 or 2)

 

 

-1,999.000 to 9,999.000

9,999

Sensor Type is set to Mil-

[ r.hi]

Range High

 

 

 

 

 

 

livolts, Volts, Milliamps

 

Set the high range for the displayed pro-

 

 

 

 

 

or Potentiometer 1 kΩ.

 

cess input units.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[`P;EE]

Input (1 or 2)

 

 

[`off] Off

 

 

Off

Sensor Type is set to Mil-

[ P.EE]

Process Error Enable

 

 

[Low] Low

 

livolts, Volts, Milliamps

 

Turn the Process Error Low feature on or

 

 

 

 

 

or Potentiometer 1 kΩ.

 

off.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Some values will be rounded off to fit in the four-character display. Full values can be read with other interfaces. If there is only one instance of a menu, no submenus will appear.

Watlow EZ-ZONE®PM Integrated Controller

34

Chapter 6 Setup Page