EtherNet/IP™ and Modbus TCP Communications
Warning:
Use National Electric (NEC) or other
unused
unused
receive -
unused
unused
receive +
transmit -
transmit +
| Slot B |
| T568B wire | Signal | Slot | |
E8 |
|
| pin | color |
| B |
E7 |
|
| 8 | brown | unused | E8 |
| ||||||
E6 |
|
| 7 | brown & white | unused | E7 |
| ||||||
E5 |
|
| 6 | green | receive - | E6 |
| ||||||
| ||||||
E4 |
| 5 | white & blue | unused | E5 | |
| ||||||
| ||||||
|
|
|
|
|
| |
E3 |
| 4 | blue | unused | E4 | |
| ||||||
| ||||||
|
|
|
|
|
| |
E2 |
| 3 | white & green | receive + | E3 | |
| ||||||
| ||||||
|
|
|
|
|
| |
| 2 | orange | transmit - | E2 | ||
E1 |
| |||||
| ||||||
|
|
|
|
|
| |
| 1 | white & orange | transmit + | E1 | ||
|
| |||||
|
|
•Do not route network wires with power wires.
•Connect one Ethernet cable per controller to a 10/100 mbps ether- net switch. Both Mod- bus TCP and Ether- Net/IP™ are available on the network.
•A RUI may be con- nected at the same time using Slot C.
injury or loss of life.
Note:
Maximum wire size termination and torque rating:
•0.0507 to 3.30 mm2 (30 to
12 AWG)
•0.8 Nm (7.0
Note:
EtherNet/IP™ and Modbus TCP communications to connect with a 10/100 switch.
DeviceNet™ Communications
V+ |
| Slot B | Terminal | Signal | Function | |||
V+ |
|
|
| |||||
|
|
|
| |||||
CAN_H |
| CH |
|
|
| V+ | V+ | DeviceNet™ power |
|
|
|
| |||||
|
|
|
| |||||
shield |
|
|
|
|
|
|
| |
| SH |
|
|
| CH | CAN_H | positive side of DeviceNet™ | |
|
|
|
| |||||
|
|
|
|
| ||||
CAN_L |
| CL |
|
|
|
|
| bus |
V- |
| V- |
|
|
| SH | shield | shield interconnect |
|
|
|
| |||||
|
|
|
| |||||
|
| T2 |
|
|
| CL | CAN_L | negative side of DeviceNet™ |
|
|
|
|
| ||||
|
| S2 |
|
|
|
|
| bus |
|
|
|
|
|
|
| ||
|
| R2 |
|
|
| V- | V- | DeviceNet™ power return |
|
|
|
|
| ||||
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
Adjacent terminals may be labeled differently, depending on the model number.
Note:
To prevent damage to the controller, do not connect wires to unused terminals.
Wiring a Serial EIA-485 Network
Do not route network wires with power wires. Connect network wires in
A termination resistor may be re-
quired. Place a 120 Ω resistor across T+/R+ and
Only one protocol per port is available at a time: either Modbus RTU or Standard Bus.
Note:
Maintain electrical isolation between analog input 1, digital
Note:
The control output common terminal and the digital common terminal are referenced to different voltages and must remain isolated.
Note:
Avoid continuous writes within loops. Excessive writes to EEPROM will cause premature EEPROM failure. The EEPROM is rated for 1,000,000 writes.
|
|
|
|
|
|
| ||||||||
ST_ _ - (B or F) _ A _ |
| ST_ _ - (B or F) _ M _ |
| |||||||||||
|
|
|
|
|
|
| power |
|
|
|
|
|
| power |
|
|
|
|
|
|
| supply |
|
|
|
|
|
| supply |
D5 | D6 | B5 | CE | CF CD | 99 | 98 | fuse | D5 | D6 | CB B5 | CC CA | 99 | 98 | fuse |
|
| |||||||||||||
|
|
| B + | A - |
| power |
|
|
| B + | A - |
| power |
|
|
|
|
|
|
|
|
| power |
| |||||
|
|
|
| power |
|
|
|
|
| |||||
|
|
|
|
| common |
|
|
|
|
| common |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 98 | power | 98 | power | ||
® | PM | power | ||||||
power | 99 | |||||||
| 99 |
|
| |||||
|
|
|
|
|
| com | ||
|
|
| CF | com |
| CC | ||
|
|
|
| - A | ||||
|
|
| CD | - A |
| CA | ||
|
|
|
|
| ||||
|
|
|
|
|
| + B | ||
|
|
| CE | + B |
| CB | ||
|
|
|
|
| ||||
|
|
|
|
|
|
| ||
|
|
| B5 |
|
| B5 |
| |
|
|
|
|
|
|
| ||
|
|
| D6 |
|
| D6 |
| |
|
|
|
|
|
|
| ||
|
|
| D5 |
|
| D5 |
| |
|
|
|
|
|
|
| ||
RUI/Gateway |
| PLC |
|
| ||||
|
|
| ||||||
|
| power |
| 98 |
|
| power | |
|
|
|
|
| power | |||
|
| power |
| 99 |
|
| ||
|
|
|
|
| common | |||
|
| common |
| CF |
|
| ||
|
|
|
|
| - A | |||
|
| - A |
| CD |
|
| ||
|
|
|
|
| + B | |||
|
| + B |
| CE |
|
| ||
|
|
|
|
|
| |||
A network using Watlow's Standard Bus | A network using Modbus RTU. | |||||||
and an RUI/Gateway. |
|
|
|
|
|
Watlow | • 23 • | Chapter 2 Install and Wire |