EZ-ZONE®PM Integrated Model 1/16 DIN with a Current Transformer — Input/Output(no communications options 2 to 3)

Universal Sensor Input, Configuration Communications,

Red/Green 7-Segment Display

Input

Functions

input sensor

none,

idle set point, alarm reset, tune, silence alarm, manual/auto mode, control outputs off, lock keypad, force alarm, TRU-TUNE+®disable loop & alarms off, profile disable, profile hold/resume, profile start, profile start/stop, restore user settings

Network

remote user interface, personal computer, programmable logic controller, human- machine interface

current transformer

Analog Input 1 thermocouple, RTD, process (V, mV, mA, 1k po- tentiometer)

Digital Input (or Output) 5

(optional) none, switch, volts dc

Digital Input (or Output) 6 (optional) none, switch, volts dc

EZ Key programmable event

EIA 485 Communications

Standard Bus, Modbus RTU (optional)

Analog Input 2

current transformer

PID

Controller

Board

Slot A

ramp-soak with 4 files (optional)

Supervisory

&

Power

Board

Slot C

Current

Transformer

Board

(optional)

Slot B

Output 1 none, switched dc/open collector, form C mechanical (5 A) or solid-state (0.5 A) relay, process (V, mA)

Output 2 none, switched dc, no-arc power control (15 A), form A mechanical (5 A) or solid-state (0.5 A) relay

Digital Output (or Input) 5 (optional) none, switched dc

Digital Output (or Input) 6 (optional) none, switched dc

Output 3 none, switched dc/open collector, form C mechanical (5 A) or solid-state (0.5 A) relay, process (V, mA)

Output 4 none, switched dc, form A mechanical (5 A) or solid-state (0.5 A) relay

Output

Functions

off, heat, cool, duplex, alarm, retransmit, event

off, heat, cool, alarm, event

off, heat, cool, alarm, event

off, heat, cool, alarm, event

off, heat, cool, alarm, event, retransmit

off, heat, cool,

alarm, event

Current Monitoring

detects heater current flow

provides an alarm indication of a failed-load issue.

Watlow EZ-ZONE®PM Integrated Controller

4

Chapter 1 Overview