Freedom SW 3K2K InvChg Owners Guide.book Page 49 Wednesday, October 9, 2013 1:34 PM
Configuring the Freedom SW using the SCP
Table 11 Charger Settings Menu Description
Item | Description | |
|
| |
Batt Type | Sets the system battery chemistry and type: Flooded, AGM, Gel, and Custom. | |
| Selecting Custom displays the Custom Settings item, which allows you to | |
| adjust the settings for each charging stage. | |
|
| |
Custom | Displays the Custom Battery Settings menu, where you can adjust | |
Settings | settings specific to your battery type and installation. It is only displayed if | |
| Custom is selected as the Batt Type. | |
|
| |
Batt | Selects the system battery capacity in amp hours. Setting the battery capacity to | |
Capacity | 0 resets the charging current to its default values. Zero Ah battery capacity | |
| implies there is no absorption exit current criteria and absorption only exits | |
| when the absorption timer (default 3hrs, range | |
|
| |
Max Chg | Sets the percentage of the maximum DC output current that is available to the | |
Rate | charger. The maximum DC output current for different models is: | |
| • | Freedom SW 2012 |
| • | Freedom SW 3012 |
| • | Freedom SW 2024 |
| • | Freedom SW 3024 |
| If multiple Freedom SWs are charging the same battery bank, set each | |
| inverter's Max Chg Rate to 1/n of the desired charge rate (where n is the | |
| number of inverter/chargers). | |
|
| |
Charge | Sets the charging method: 3Stage (bulk, absorption, float) or 2StgNoFloat | |
Cycle | (bulk, absorption, no float). | |
|
| |
ReCharge | Sets the recharging volts to tell the charger to initiate charging when the battery | |
Volts | drains past the value setting. | |
|
| |
Auto | Enables or disables automatic charging. When there are two or more power | |
ReCharge | sources for charging batteries, Auto ReCharge can be disabled to allow | |
| manual charging of batteries. | |
|
|
|
Table 11 Charger Settings Menu Description
Item | Description |
|
|
Absorb | Sets the maximum time spent in the absorption stage, before transitioning to float |
Time | or no float. |
| NOTE: The Absorb Time setting resets to its default value of 180 minutes when the |
| Battery Type is changed except when changing to Custom Settings. In Custom |
| Settings, the Absorb Time setting will not reset to its default value. |
|
|
Default | Selects the battery temperature charging compensation if a battery temperature |
Batt Temp | sensor is not installed. In the absence of a battery temperature sensor, the |
| charger uses one of three settings: Cold (5 °C/41 °F), Warm (25 °C/77 °F), or |
| Hot (40 °C/104 °F). |
|
|
Battery Charger Functions
When AC power is available, the Freedom SW can operate as a battery charger. Different battery types and chemistries require different charging voltage levels. Not charging batteries at the required levels can shorten battery life or damage the batteries. The Freedom SW is configured at the factory to work with the battery types recommended for inverter applications. If the default settings do not work for your specific installation, you can adjust the charge stage settings (as recommended by the battery manufacturer) on the Custom (Battery) Settings menu (see page 50).
NOTE: This information is provided for guidance only. Variations in battery chemistry and
|
| 49 |
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|