Freedom SW 3K2K InvChg Owners Guide.book Page 53 Wednesday, October 9, 2013 1:34 PM

Configuring the Freedom SW using the SCP

Gen Support

GEN Support allows power to be automatically drawn from the batteries to assist an AC generator to support heavy loads (i.e., loads that exceed the available current from the generator).

Generators have a limited output current and it is possible to reach this limit when operating heavy loads. The Freedom SW is designed to assist the generator when heavy current demands load down the generator by supplying additional power from the batteries.

In addition, the battery charger can reduce its charging current to the batteries so the combined charge AC current and total load current does not exceed the capacity of the generator or trip its output breakers or fuses.

FSW3012 00: GEN Support

 

GenSup Mode

[Disabled]

[*Disabled] [Enabled]

GenSup Amps

[30A]

 

 

 

 

Follow procedures on “To select and change a configurable setting:” on page 33 to change the settings.

Table 16 GEN Support Menu Description and Valuesa

Setting

Description

Default

Range

 

 

 

 

GenSup Mode

Turns the generator support

Disabled

Disabled,

 

feature on and off.

 

Enabled

GenSup Amps

Sets the generator load level

24A

4A to 24A

 

at which the Freedom SW

 

 

 

supplies power from the

 

 

 

batteries to support the

 

 

 

generator.

 

 

 

 

 

 

a. Applies to all Freedom SW models.

The Freedom SW supports the generator (or other power source) when the AC load current drawn from the generator exceeds the GenSup Amps setting for one to two seconds.

The system can enter this state if the battery voltage is above Low Battery CutOut (LBCO) plus 1 volt and generator support is enabled.

Figure 28 GEN Support Menu Screen

NOTE: Running and start-up (peak) currents are limited to the maximum current limits of the inverter.

 

 