Configuring the Freedom SW using the SCP
Table 6 Setting Defaults and Ranges
Model | Freedom SW 2012 / 3012 | Freedom SW 2024 / 3024 | ||||||
|
|
|
|
|
|
|
|
|
Item | Default |
| Min | Max | Default |
| Min | Max |
|
|
|
|
|
|
|
|
|
Batt Type | Flooded |
| Flooded, Gel, | Flooded |
| Flooded, Gel, | ||
|
|
| AGM, Custom |
|
| AGM, Custom | ||
|
|
|
|
|
|
|
|
|
Batt Capacity | 250Ah |
| 50Ah | 2000Ah | 250Ah |
| 50Ah | 1000Ah |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
Batt Capacity | 440Ah |
|
|
| 440Ah |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
Max Chg Rate | 100% | 10% | 100% | 100% | 10% | 100% | ||
|
|
|
|
|
|
|
|
|
Charge Cycle | 3Stage |
| 3Stage, | 3Stage |
| 3Stage, | ||
|
|
| 2StgNoFloat |
|
| 2StgNoFloat | ||
|
|
|
|
|
|
|
|
|
ReCharge Volts | 12.5V |
| 11.0V | 13.5V | 25.0V |
| 22.0V | 27.0V |
|
|
|
|
|
|
|
|
|
AC1 Breaker | 30A |
| 5A | 30A | 30A |
| 5A | 30A |
|
|
|
|
|
|
|
|
|
Low Batt Cut Out | 10.5V |
| 10.0V | 12.0V | 21.0V |
| 20.0V | 24.0V |
|
|
|
|
|
|
|
|
|
Table 7 Basic Settings
Item | Description | |
|
| |
Batt Type | Sets the system battery chemistry and type: Flooded, AGM, Gel, and | |
| Custom. | |
| Selecting Custom displays the Custom Settings item, which | |
| allows you to adjust the settings for each charging stage. | |
Batt Capacity | Selects the system battery capacity in amp hours. Setting the battery | |
| capacity to 0 resets the charging current to its default values. | |
| Zero Ah battery capacity implies there is no absorption exit current | |
| criteria and absorption only exits when the absorption timer (default | |
| 3hrs, range | |
Max Chg Rate | Sets the percentage of the maximum DC output current that is | |
| available to the charger. The maximum DC output current for | |
| different models is: | |
| • | Freedom SW 2012 |
| • | Freedom SW 3012 |
| • | Freedom SW 2024 |
| • | Freedom SW 3024 |
| If multiple Freedom SWs are charging the same battery bank, set | |
| each inverter's Max Chg Rate to 1/n of the desired charge rate | |
| (where n is the number of inverter/chargers). | |
Charge Cycle | Sets the charging method: | |
| 2StgNoFloat (bulk, absorption, no float). | |
ReCharge Volts | Sets the recharging volts to tell the charger to initiate charging when | |
| the battery drains past the value setting. | |
AC In Breaker | Set the breaker limit of incoming AC. | |
|
| |
Low Batt Cut Out | Low Battery Cut Out (LBCO) controls when the inverter stops | |
| producing AC output due to a low battery voltage condition. The | |
| inverter will stop producing AC output only after this level has been | |
| reached for the period of time set by the LBCO Delay. This setting is | |
| not temperature compensated. | |
|
|
|
|
| 39 |
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|