Troubleshooting
Table 5 provides a detailed description of the warning messages and solutions. If you are unable to resolve the problem after referring to this table, contact your dealer or Customer Service.
Table 5 Warning Messages
Fault |
|
|
|
|
Number | Message | Fault Type | Cause | Solution |
|
|
|
|
|
W48 | DC under voltage | Automatic | Voltage at the DC input | Check for the correct battery voltage at the |
| (Warning) |
| terminals is below the Low | inverter's DC input terminals. |
|
|
| Battery Cut Out (LBCO) | Check for external DC loads on the |
|
|
| setting. | batteries. |
|
|
|
| Check condition of batteries and recharge |
|
|
|
| if necessary. |
|
|
|
| Reduce the Low Battery Cut Out (LBCO) |
|
|
|
| setting. |
|
|
|
| Battery bank capacity may be inadequate |
|
|
|
| for the loads in the system. |
|
|
|
|
|
W69 | AGS not connected | Automatic | The GenSup Mode setting | Install a Xanbus AGS on the network or |
|
|
| is enabled but there is no | disable the GenSup Mode setting. |
|
|
| AGS connected in the |
|
|
|
| Xanbus network. |
|
|
|
|
|
|
|