Battery Charging Reference
The charging cycle is a
Bulk Stage | Absorption Stage | Float Stage |
Battery |
|
|
Voltage |
|
|
| Absorption Voltage |
|
| Float Voltage | |
|
| |
|
| Time |
Max Absorb Time - Dflt 3 hrs (adjustable 1 min - 8 hrs)
Battery
Current
Max Charge
Rate
Absorption Exit Current
Threshold = 2% of programmed AH capacity
NOTE:
When the charge cycle is interrupted, the charger will restart charging at the beginning of the
Exit Current Threshold can be effectively disabled by programming the
Charge current during equalize state (optional state not shown here) is normally limited to 10% of the programmed
Synchronized charge states are active when more than one charging device is connected in the system via the Xanbus network.
•The first unit (Freedom SW) to enter bulk, causes all other chargers to enter bulk.
•The first Freedom SW to enter absorption causes all other Freedom SWs to enter absorption.
•The last Freedom SW ready to exit absorption triggers all Freedom SWs to exit absorption and exit charge.
Bulk Stage
Time
Figure 32
Bulk charge is the first stage in the charging process and provides the batteries with a controlled, constant current. Once the battery voltage rises to the absorption voltage threshold, the charger switches to the absorption stage.
|
| 59 |
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|