Troubleshooting
Table 4 provides a detailed description of the fault messages and solutions. If you are unable to resolve the problem after referring to this table, contact your dealer or Customer Service.
Table 4 Fault Messages
Fault |
|
|
|
|
Number | Message | Fault Type | Cause | Solution |
|
|
|
|
|
F1 | AC Output under | Escalating Auto Fault. | Inverter voltage is under | Remove excessive load. |
| voltage | Must occur 3 times in 30 | 100 volts. |
|
|
| seconds before becoming a |
|
|
|
| manual fault. |
|
|
|
|
|
|
|
F2 | AC Output over | Escalating Auto Fault. | Inverter voltage is over 135 | Check if there is an external power source |
| voltage | Must occur 3 times in 30 | volts. | that is running parallel to the inverter’s |
|
| seconds before becoming a |
| output. |
|
| manual fault. |
|
|
|
|
|
|
|
F17 | Relays Welded | Manual | AC backfeed from welded | Service required. |
|
|
| relay. |
|
|
|
|
|
|
|