Hitachi hitachi series inverter user manual Forward Run/Stop and Reverse Run/Stop Commands

Page 33

Forward Run/Stop and Reverse Run/Stop Commands:

When you input the Run command via the terminal [FW], the inverter executes the Forward Run command (high) or Stop command (low). When you input the Run command via the terminal [RV], the inverter executes the Reverse Run command (high) or Stop command (low).

Option Terminal Code Symbol

Function Name

State

Description

00

FW

Forward Run/Stop

 

ON

Inverter is in Run Mode, motor runs forward

 

 

 

 

 

OFF

Inverter is in Stop Mode, motor stops

01

RV

Reverse Run/Stop

 

ON

Inverter is in Run Mode, motor runs reverse

 

 

 

 

 

OFF

Inverter is in Stop Mode, motor stops

 

 

 

C001 C007

 

Example (default input configuration shown see

 

 

 

~

 

 

page 66):

 

 

 

A002 = 01

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

RV FW

 

When the Forward Run and Reverse Run

 

 

 

 

 

 

 

 

 

 

7

6

5

4

3

2

1

L

 

 

 

P24

 

 

commands are active at the same time, the

 

 

PLC

 

 

inverter enters the Stop Mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When a terminal associated with either [FW] or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[RV] function is configured for normally closed,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the motor starts rotation when that terminal is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

disconnected or otherwise has no input voltage.

See I/O specs on page 21,22.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: The parameter F004, Keypad Run Key Routing, determines whether the single Run key issues a Run FWD command or Run REV command. However, it has no effect on the [FW] and [RV] input terminal operation.

WARNING: If the power is turned ON and the Run command is already active, the motor starts rotation and is dangerous! Before turning power ON, confirm that the Run command is not active.

31

Image 33
Contents WJ200 Series Inverter Quick Reference Guide Page UL→ Cautions, Warnings and Instructions Marking RequirementsTerminal symbols and Screw size Fuse Sizes 5AT 123 45A-001 1005 Inverter Specification LabelModel-specific tables for 200V and 400V class inverters WJ200 Inverter SpecificationsWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Basic System Description GFIInverter + Determining Wire and Fuse Sizes Motor OutputAllowable current T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3 Wire the Inverter Input to a SupplyRB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Using the Front Panel Keypad Key and Indicator LegendPower LED Alarm LED Keys, Modes, and Parameters Keypad Navigation MapPRG LED Group F Group dSave Group aF001 Key GND Connecting to PLCs and Other DevicesMotor Example Wiring DiagramPulse Control Logic Signal SpecificationsTrain Output InputSP, SN Wiring sample of control logic terminal sink logicSink/source logic of intelligent input terminals Wire size for control and relay terminalsRecommended ferrule Intelligent Inputs Intelligent Terminal ListingIntelligent Outputs Using Intelligent Input Terminals Sink logic connectionSource logic connection Sinking Inputs, Internal Supply WJ200Sourcing Inputs, Internal Supply Sourcing Inputs, External Supply Sinking Inputs, External SupplyOFF InsertingOption Terminal Code Symbol Function Name State Description Forward Run/Stop and Reverse Run/Stop CommandsMulti-Speed Select ~Binary Operation Required settingsTwo Stage Acceleration and Deceleration FW,RV2CH Option Terminal Function Name State Description Code Symbol Unattended Start ProtectionUSP Reset Inverter Run Signal Using Intelligent Output TerminalsCode Symbol Option Terminal Function NameFrequency Arrival Signals SettingsRequired FA3/FA5 FA2/FA4Alarm Signal StopTrip During normal operation Analog Input Operation AM H O OI LAM H O OI Other Analog Input-related topics SN 7 6 5 4 3 2 1 L PLC P24 Pulse Train Input OperationAnalog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D007 D006D008 D009D030 D029D050 D060Main Profile Parameters Standard Functions A220 A015A241 A021 ~ A035A043 A242A243 A044A059 A058A061 A261A073 A072A074 A075A292 A092A093 A293A132 A131A141 A142A157 A156A161 A162Fine Tuning Functions B212 B012B013 B213B026 B025B027 B028B038 B037B039 B040B061 B060B062 B063B088 B087B089 B090B097 B096B100 B101B134 B133B145 B150Intelligent Terminal Functions C030 C028C031 C032C052 C047C053 C054C077 C076C078 C081C103 C102C104 C105C148 C147C149 C150FWD, REV AnlgPidc DWNSF2 SF1SF3 SF4255 Run Signal When the inverter is in Run Mode LOG1 LOG2LOG3 MO1 C039MO2 MO3Motor Constants Functions PM Motor Constants Functions H113 H112H116 H117Expansion Card Functions P044 P041P045 P046P073 P072P075 P077Trip History and Inverter Status Monitoring Trip Events, History, & ConditionsError Name Causes Code Error CodesE37 Restoring Factory Default Settings Error Name Descriptions CodeOther indication Important notes CE-EMC Installation GuidelinesPage Page Metal plate earth Installation for WJ200 series example of SF modelsHitachi EMC Recommendations Introduction Functional Safety Certification in ProgressStop Category defined in EN60204-1 How it worksInstallation Wiring example OFF GS9A G9SXNE1A