(When safety switch or EDM switch is turned off, the intelligent input and output terminal assigned on will be set as "no" function, and contact will remain normally off.)

Always use both inputs to disable the drive. If for any reason only one channel is opened, the drive output is stopped but the EDM output is not activated. In this case the Safe Disable input wiring must be checked.

Installation

According to the safety standard listed above, please install referring to the example. Please be sure to use the both GS1 and GS2, and construct the system that GS1 andGS2 are both turned off when safety input is given to the inverter.

When the Gate Suppress function is utilized, connect the drive to a safety certified interrupting device utilizing EDM output signal to reconfirm both safety inputs GS1 and GS2.

item

Function

data

description

code

 

 

 

 

Input [3] and [4]

C003

77

GS1: Safety input 1 (note 1)

function

C004

78

GS2Safety input 2 (note 1)

Input [3] and [4]

C013

01

NC: Normally Closed

(note 1)

active state

C014

01

NC: Normally Closed

(note 1)

Output [11] function

C021

62

EDMExternal Device Monitor(note2)

Output [11] active

C031

00

NO: Normally Open

(note 2)

state

 

 

 

 

GS input mode

b145

00

Output is shut off by hardware. No trip.

01

Output is shut off by hardware, and then,

 

 

trip. (note3) (note4)

 

 

 

 

 

Note 1) They are automatically set when safety switch is turned ON, cannot be changed.

Note 2) Those are automatically assigned when EDM switch is turned ON, cannot be changed.

Note 3) Inverter trips with "E37". When competing with external trip (E12), E37 has priority.

Note 4) While the drive is the trip status "E037" and either GS1 or GS2 is activated, on the safety by is not guaranteed.

94

Image 96
Contents WJ200 Series Inverter Quick Reference Guide Page Marking Requirements UL→ Cautions, Warnings and InstructionsTerminal symbols and Screw size Fuse Sizes Inverter Specification Label 5AT 123 45A-001 1005WJ200 Inverter Specifications Model-specific tables for 200V and 400V class invertersWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Basic System Description GFIInverter + Determining Wire and Fuse Sizes Motor OutputAllowable current Wire the Inverter Input to a Supply T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3RB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Using the Front Panel Keypad Key and Indicator LegendPower LED Alarm LED Keys, Modes, and Parameters Keypad Navigation MapPRG LED Group d Group FSave Group aF001 Key Connecting to PLCs and Other Devices GNDExample Wiring Diagram MotorControl Logic Signal Specifications PulseTrain Output InputWiring sample of control logic terminal sink logic SP, SNWire size for control and relay terminals Sink/source logic of intelligent input terminalsRecommended ferrule Intelligent Terminal Listing Intelligent InputsIntelligent Outputs Using Intelligent Input Terminals Sink logic connectionSource logic connection Sinking Inputs, Internal Supply WJ200Sourcing Inputs, Internal Supply Sinking Inputs, External Supply Sourcing Inputs, External SupplyInserting OFFForward Run/Stop and Reverse Run/Stop Commands Option Terminal Code Symbol Function Name State DescriptionRequired settings Multi-Speed Select ~Binary OperationTwo Stage Acceleration and Deceleration FW,RV2CH Option Terminal Function Name State Description Code Symbol Unattended Start ProtectionUSP Reset Inverter Using Intelligent Output Terminals Run SignalCode Symbol Option Terminal Function NameFrequency Arrival Signals SettingsRequired FA2/FA4 FA3/FA5Alarm Signal StopTrip During normal operation Analog Input Operation AM H O OI LAM H O OI Other Analog Input-related topics Pulse Train Input Operation SN 7 6 5 4 3 2 1 L PLC P24Analog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D006 D007D008 D009D029 D030D050 D060Main Profile Parameters Standard Functions A015 A220A241 A021 ~ A035A242 A043A243 A044A058 A059A061 A261A072 A073A074 A075A092 A292A093 A293A131 A132A141 A142A156 A157A161 A162Fine Tuning Functions B012 B212B013 B213B025 B026B027 B028B037 B038B039 B040B060 B061B062 B063B087 B088B089 B090B096 B097B100 B101B133 B134B145 B150Intelligent Terminal Functions C028 C030C031 C032C047 C052C053 C054C076 C077C078 C081C102 C103C104 C105C147 C148C149 C150Anlg FWD, REVPidc DWNSF1 SF2SF3 SF4255 Run Signal When the inverter is in Run Mode LOG1 LOG2LOG3 C039 MO1MO2 MO3Motor Constants Functions PM Motor Constants Functions H112 H113H116 H117Expansion Card Functions P041 P044P045 P046P072 P073P075 P077Monitoring Trip Events, History, & Conditions Trip History and Inverter StatusError Codes Error Name Causes CodeE37 Restoring Factory Default Settings Error Name Descriptions CodeOther indication CE-EMC Installation Guidelines Important notesPage Page Installation for WJ200 series example of SF models Metal plate earthHitachi EMC Recommendations Functional Safety Certification in Progress IntroductionStop Category defined in EN60204-1 How it worksInstallation Wiring example OFF GS9A G9SXNE1A