Hitachi hitachi series inverter Functional Safety Certification in Progress, Introduction

Page 95

Functional Safety (Certification in Progress)

Introduction

The Gate Suppress function can be utilized to perform a safe stop according to the EN60204-1, stop category 0 (Uncontrolled stop by power removal). It is designed to meet the requirements of the ISO13849-1, PL=d only in a system in which EDM signal is monitored by an “external device monitor”.

Stop Category defined in EN60204-1

Category 0 : Uncontrolled stop by immediate (< 200 ms) shut-down of the power supply to the actuators

Category 1 : Controlled stop by interrupting the power supply to the actuator level if, for example, the hazardous movement has been brought to a standstill (time-delayed shut-down of the power supply).

Category 2 : Controlled stop. The power supply to the drive element is not interrupted. Additional measures to EN 1037 (protection from unexpected restart) are necessary.

How it works

Interrupting the current to GS1 or GS2, for example removing the link between either GS1 or GS2 and PLC or both GS1/GS2 and PLC disables the drive output, i.e. the power supply to the motor is cut by stopping the switching of the output transistors in a safe way. EDM output is activated when GS1 and GS2 are given to the drive.

Always use both inputs to disable the drive. If for any reason only one channel is opened, the drive output is stopped but the EDM output is not activated. In this case the Safe Disable input wiring must be checked.

Activation

Turning on the safety switch automatically assign the GS1 input and GS2 input automatically.

To assign EDM (external device monitor) output, please turn the EDM function switch on. EDM output is automatically assigned on intelligent output terminal 11.

Safety function

 

EDM function

 

 

 

 

 

 

 

 

 

switch

 

 

switch

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

ON

OFF

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

(normal)

 

 

 

 

(EDM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

93

Image 95
Contents WJ200 Series Inverter Quick Reference Guide Page UL→ Cautions, Warnings and Instructions Marking RequirementsTerminal symbols and Screw size Fuse Sizes 5AT 123 45A-001 1005 Inverter Specification LabelModel-specific tables for 200V and 400V class inverters WJ200 Inverter SpecificationsWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Inverter + Basic System DescriptionGFI Allowable current Determining Wire and Fuse SizesMotor Output T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3 Wire the Inverter Input to a SupplyRB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Power LED Alarm LED Using the Front Panel KeypadKey and Indicator Legend PRG LED Keys, Modes, and ParametersKeypad Navigation Map Group a Group dGroup F SaveF001 Key GND Connecting to PLCs and Other DevicesMotor Example Wiring DiagramOutput Input Control Logic Signal SpecificationsPulse TrainSP, SN Wiring sample of control logic terminal sink logicSink/source logic of intelligent input terminals Wire size for control and relay terminalsRecommended ferrule Intelligent Inputs Intelligent Terminal ListingIntelligent Outputs Source logic connection Using Intelligent Input TerminalsSink logic connection Sourcing Inputs, Internal Supply Sinking Inputs, Internal SupplyWJ200 Sourcing Inputs, External Supply Sinking Inputs, External SupplyOFF InsertingOption Terminal Code Symbol Function Name State Description Forward Run/Stop and Reverse Run/Stop CommandsMulti-Speed Select ~Binary Operation Required settings2CH Two Stage Acceleration and DecelerationFW,RV USP Option Terminal Function Name State Description Code SymbolUnattended Start Protection Reset Inverter Option Terminal Function Name Using Intelligent Output TerminalsRun Signal Code SymbolRequired Frequency Arrival SignalsSettings FA3/FA5 FA2/FA4Trip Alarm SignalStop During normal operation AM H O OI Analog Input OperationAM H O OI L Other Analog Input-related topics SN 7 6 5 4 3 2 1 L PLC P24 Pulse Train Input OperationAnalog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D009 D006D007 D008D060 D029D030 D050Main Profile Parameters Standard Functions A021 ~ A035 A015A220 A241A044 A242A043 A243A261 A058A059 A061A075 A072A073 A074A293 A092A292 A093A142 A131A132 A141A162 A156A157 A161Fine Tuning Functions B213 B012B212 B013B028 B025B026 B027B040 B037B038 B039B063 B060B061 B062B090 B087B088 B089B101 B096B097 B100B150 B133B134 B145Intelligent Terminal Functions C032 C028C030 C031C054 C047C052 C053C081 C076C077 C078C105 C102C103 C104C150 C147C148 C149DWN AnlgFWD, REV PidcSF4 SF1SF2 SF3255 Run Signal When the inverter is in Run Mode LOG3 LOG1LOG2 MO3 C039MO1 MO2Motor Constants Functions PM Motor Constants Functions H117 H112H113 H116Expansion Card Functions P046 P041P044 P045P077 P072P073 P075Trip History and Inverter Status Monitoring Trip Events, History, & ConditionsError Name Causes Code Error CodesE37 Other indication Restoring Factory Default SettingsError Name Descriptions Code Important notes CE-EMC Installation GuidelinesPage Page Metal plate earth Installation for WJ200 series example of SF modelsHitachi EMC Recommendations How it works Functional Safety Certification in ProgressIntroduction Stop Category defined in EN60204-1Installation Wiring example OFF NE1A GS9AG9SX