Hitachi hitachi series inverter user manual A015, A220, A241, A021 ~ A035

Page 53

 

 

 

 

 

 

 

 

Func.

 

Name

 

Description

 

 

Code

 

 

 

 

 

 

 

 

 

Run

Mode

Edit

Initialdata Units

A015

[O] input start frequency

Two options; select codes:

 

01

enable

00Use offset (A011 value)

 

 

 

 

 

01Use 0Hz

 

 

 

A016

Analog input filter

Range n = 1 to 31,

 

8.

Spl.

 

 

1 to 30 : ×2ms filter

 

 

 

 

 

31: 500ms fixed filter with ±

 

 

 

 

 

0.1kHz hys.

 

 

 

A017

 

 

 

 

00

-

 

 

 

 

 

 

 

a019

Multi-speed operation

Select codes:

 

00

-

selection

00

 

 

 

 

...Binary operation (16 speeds

 

 

 

 

 

selectable with 4 terminals)

 

 

 

 

 

01...Bit operation (8 speeds

 

 

 

 

 

selectable with 7 terminals)

 

 

 

A020

Multi-speed freq. 0

Defines the first speed of a

 

0.0

Hz

 

 

multi-speed profile, range is 0.0 /

 

 

 

 

 

start frequency to 400Hz

 

 

 

 

 

A020 = Speed 0 (1st motor)

 

 

 

A220

Multi-speed freq. 0,

Defines the first speed of a

 

 

0.0

Hz

2nd motor

multi-speed profile or a 2nd

 

 

 

 

 

 

motor, range is 0.0 / start

 

 

 

 

 

 

frequency to 400Hz

 

 

 

 

 

 

A220 = Speed 0 (2nd motor)

 

 

 

 

A021

Multi-speed freq. 1 to 15

Defines 15 more speeds,

 

 

See next

Hz

to

(for both motors)

range is 0.0 / start frequency to

 

 

row

 

A035

 

400 Hz.

 

 

 

 

 

A021=Speed 1 ~ A035=Speed15

 

 

 

 

 

 

 

 

 

 

 

 

A021 ~ A035

 

 

0.0

Hz

 

 

 

 

 

 

 

A038

Jog frequency

Defines limited speed for jog,

 

 

6.00

Hz

 

 

range is from start frequency to

 

 

 

 

 

 

9.99 Hz

 

 

 

 

A039

Jog stop mode

Define how end of jog stops the

 

 

04

 

 

motor; six options:

 

 

 

 

 

 

00Free-run stop (invalid during

 

 

 

 

 

 

run)

 

 

 

 

 

 

01Controlled deceleration

 

 

 

 

 

 

(invalid during run)

 

 

 

 

 

 

02DC braking to stop(invalid

 

 

 

 

 

 

during run)

 

 

 

 

 

 

03Free-run stop (valid during

 

 

 

 

 

 

run)

 

 

 

 

 

 

04Controlled deceleration

 

 

 

 

 

 

(valid during run)

 

 

 

 

 

 

05DC braking to stop(valid

 

 

 

 

 

 

during run)

 

 

 

 

A041

Torque boost select

Two options:

 

 

00

 

 

00Manual torque boost

 

 

 

 

 

Torque boost select, 2nd motor

01Automatic torque boost

 

 

 

 

A241

 

00

 

 

 

 

 

 

 

 

 

A042

Manual torque boost value

Can boost starting torque

 

1.0

%

 

 

between 0 and 20% above

 

 

 

 

 

 

 

 

 

 

51

Image 53
Contents WJ200 Series Inverter Quick Reference Guide Page UL→ Cautions, Warnings and Instructions Marking RequirementsTerminal symbols and Screw size Fuse Sizes 5AT 123 45A-001 1005 Inverter Specification LabelModel-specific tables for 200V and 400V class inverters WJ200 Inverter SpecificationsWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Inverter + Basic System DescriptionGFI Allowable current Determining Wire and Fuse SizesMotor Output T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3 Wire the Inverter Input to a SupplyRB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Power LED Alarm LED Using the Front Panel KeypadKey and Indicator Legend PRG LED Keys, Modes, and ParametersKeypad Navigation Map Group F Group dSave Group aF001 Key GND Connecting to PLCs and Other DevicesMotor Example Wiring DiagramPulse Control Logic Signal SpecificationsTrain Output InputSP, SN Wiring sample of control logic terminal sink logicSink/source logic of intelligent input terminals Wire size for control and relay terminalsRecommended ferrule Intelligent Inputs Intelligent Terminal ListingIntelligent Outputs Source logic connection Using Intelligent Input TerminalsSink logic connection Sourcing Inputs, Internal Supply Sinking Inputs, Internal SupplyWJ200 Sourcing Inputs, External Supply Sinking Inputs, External SupplyOFF InsertingOption Terminal Code Symbol Function Name State Description Forward Run/Stop and Reverse Run/Stop CommandsMulti-Speed Select ~Binary Operation Required settings2CH Two Stage Acceleration and DecelerationFW,RV USP Option Terminal Function Name State Description Code SymbolUnattended Start Protection Reset Inverter Run Signal Using Intelligent Output TerminalsCode Symbol Option Terminal Function NameRequired Frequency Arrival SignalsSettings FA3/FA5 FA2/FA4Trip Alarm SignalStop During normal operation AM H O OI Analog Input OperationAM H O OI L Other Analog Input-related topics SN 7 6 5 4 3 2 1 L PLC P24 Pulse Train Input OperationAnalog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D007 D006D008 D009D030 D029D050 D060Main Profile Parameters Standard Functions A220 A015A241 A021 ~ A035A043 A242A243 A044A059 A058A061 A261A073 A072A074 A075A292 A092A093 A293A132 A131A141 A142A157 A156A161 A162Fine Tuning Functions B212 B012B013 B213B026 B025B027 B028B038 B037B039 B040B061 B060B062 B063B088 B087B089 B090B097 B096B100 B101B134 B133B145 B150Intelligent Terminal Functions C030 C028C031 C032C052 C047C053 C054C077 C076C078 C081C103 C102C104 C105C148 C147C149 C150FWD, REV AnlgPidc DWNSF2 SF1SF3 SF4255 Run Signal When the inverter is in Run Mode LOG3 LOG1LOG2 MO1 C039MO2 MO3Motor Constants Functions PM Motor Constants Functions H113 H112H116 H117Expansion Card Functions P044 P041P045 P046P073 P072P075 P077Trip History and Inverter Status Monitoring Trip Events, History, & ConditionsError Name Causes Code Error CodesE37 Other indication Restoring Factory Default SettingsError Name Descriptions Code Important notes CE-EMC Installation GuidelinesPage Page Metal plate earth Installation for WJ200 series example of SF modelsHitachi EMC Recommendations Introduction Functional Safety Certification in ProgressStop Category defined in EN60204-1 How it worksInstallation Wiring example OFF NE1A GS9AG9SX