Hitachi hitachi series inverter user manual Alarm Signal, Stop, Trip

Page 41

Alarm Signal

The inverter alarm signal is active when a fault has

occurred and it is in the Trip Mode (refer to theRun diagram at right). When the fault is cleared the alarm

signal becomes inactive.

STOP

RESET

Stop

RUN

STOP

RESET

We must make a distinction between the alarm signal

Trip

 

AL and the alarm relay contacts [AL0], [AL1] and [AL2]. Fault

Fault

The signal AL is a logic function, which you can assign

 

 

to the open collector output terminals [11], [12], or the

Alarm signal active

relay outputs.

 

 

The most common (and default) use of the relay is for AL, thus the labeling of its terminals. Use an open collector output (terminal [11] or [12]) for a low-current logic signal interface or to energize a small relay (50 mA maximum). Use the relay output to interface to higher voltage and current devices (10 mA minimum).

Option Terminal Code Symbol

Function Name

State

Description

05

AL

Alarm Signal

ON

when an alarm signal has occurred and has not

 

been cleared

OFF

when no alarm has occurred since the last clearing

 

of alarm(s)

11, 12, AL0 – AL2

C031, C032, C036

Notes:

By default, the relay is configured as normally closed (C036=01). Refer to the next page for an explanation.

In the default relay configuration, an inverter power loss turns ON the alarm output. the alarm signal remains ON as long as the external control circuit has power.

When the relay output is set to normally closed, a time delay of less than 2 seconds occurs after powerup before the contact is closed.

Terminals [11] and [12] are open collector outputs, so the electric specifications of [AL] are different from the contact output terminals [AL0], [AL1], [AL2].

This signal output has the delay time (300 ms nominal) from the fault alarm output.

The relay contact specifications are in “Control Logic Signal Specifications” on page 4–6. The contact diagrams for different conditions are on the next page.

Example for terminal [11] (default output configuration shown see page 66):

Inverter output

AL

terminal circuit

CM2

11

RY

Example for terminal [AL0], [AL1], [AL2] (requires output configuration see page 66):

Inverter logic

AL

circuit board

 

AL0

AL1 AL2

 

 

 

 

 

Power

 

 

 

 

Load

supply

 

 

 

 

 

 

 

 

 

See I/O specs on page 21,22.

39

Image 41
Contents WJ200 Series Inverter Quick Reference Guide Page UL→ Cautions, Warnings and Instructions Marking RequirementsTerminal symbols and Screw size Fuse Sizes 5AT 123 45A-001 1005 Inverter Specification LabelModel-specific tables for 200V and 400V class inverters WJ200 Inverter SpecificationsWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Inverter + Basic System DescriptionGFI Allowable current Determining Wire and Fuse SizesMotor Output T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3 Wire the Inverter Input to a SupplyRB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Power LED Alarm LED Using the Front Panel KeypadKey and Indicator Legend PRG LED Keys, Modes, and ParametersKeypad Navigation Map Group F Group dSave Group aF001 Key GND Connecting to PLCs and Other DevicesMotor Example Wiring DiagramPulse Control Logic Signal SpecificationsTrain Output InputSP, SN Wiring sample of control logic terminal sink logicSink/source logic of intelligent input terminals Wire size for control and relay terminalsRecommended ferrule Intelligent Inputs Intelligent Terminal ListingIntelligent Outputs Source logic connection Using Intelligent Input TerminalsSink logic connection Sourcing Inputs, Internal Supply Sinking Inputs, Internal SupplyWJ200 Sourcing Inputs, External Supply Sinking Inputs, External SupplyOFF InsertingOption Terminal Code Symbol Function Name State Description Forward Run/Stop and Reverse Run/Stop CommandsMulti-Speed Select ~Binary Operation Required settings2CH Two Stage Acceleration and DecelerationFW,RV USP Option Terminal Function Name State Description Code SymbolUnattended Start Protection Reset Inverter Run Signal Using Intelligent Output Terminals Code Symbol Option Terminal Function NameRequired Frequency Arrival SignalsSettings FA3/FA5 FA2/FA4Trip Alarm SignalStop During normal operation AM H O OI Analog Input OperationAM H O OI L Other Analog Input-related topics SN 7 6 5 4 3 2 1 L PLC P24 Pulse Train Input OperationAnalog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D007 D006D008 D009D030 D029D050 D060Main Profile Parameters Standard Functions A220 A015A241 A021 ~ A035A043 A242A243 A044A059 A058A061 A261A073 A072A074 A075A292 A092A093 A293A132 A131A141 A142A157 A156A161 A162Fine Tuning Functions B212 B012B013 B213B026 B025B027 B028B038 B037B039 B040B061 B060B062 B063B088 B087B089 B090B097 B096B100 B101B134 B133B145 B150Intelligent Terminal Functions C030 C028C031 C032C052 C047C053 C054C077 C076C078 C081C103 C102C104 C105C148 C147C149 C150FWD, REV AnlgPidc DWNSF2 SF1SF3 SF4255 Run Signal When the inverter is in Run Mode LOG3 LOG1LOG2 MO1 C039MO2 MO3Motor Constants Functions PM Motor Constants Functions H113 H112H116 H117Expansion Card Functions P044 P041P045 P046P073 P072P075 P077Trip History and Inverter Status Monitoring Trip Events, History, & ConditionsError Name Causes Code Error CodesE37 Other indication Restoring Factory Default SettingsError Name Descriptions Code Important notes CE-EMC Installation GuidelinesPage Page Metal plate earth Installation for WJ200 series example of SF modelsHitachi EMC Recommendations Introduction Functional Safety Certification in ProgressStop Category defined in EN60204-1 How it worksInstallation Wiring example OFF NE1A GS9AG9SX