Analog Input Operation

The WJ200 inverters provide for analog input to command the inverter frequency output value. The analog input terminal group includes the [L], [OI], [O], and [H] terminals on the control connector, which provide for Voltage [O] or Current [OI] input. All analog input signals must use the analog ground [L].

If you use either the voltage or current analog input, you must select one of them using the logic input terminal function [AT] analog type. Refer to the table on next page showing the activation of

each analog input by combination of A005 set parameter and [AT] terminal condition. The [AT] terminal function is covered in “Analog Input Current/Voltage Select” in section 4. Remember that you must also set A001 = 01 to select analog input as the frequency source.

AM H O OI L

+V Ref.

Voltage input

Current input

A GND

V/I input

 

select

A001

[AT]

Freq.

 

 

setting

AM H O OI

L

 

4-20 mA

+ -

0-10 V

NOTE: If no logic input terminal is configured for the [AT] function, then inverter recognizes that [AT]=OFF and MCU recognizes [O]+[OI] as analog input.

Using an external potentiometer is a common way to control the inverter output frequency (and a good way to learn how to use the analog inputs). The potentiometer uses the built-in 10V reference [H] and the analog ground [L] for excitation, and the voltage input [O] for the signal. By default, the [AT] terminal selects the voltage input when it is OFF.

Take care to use the proper resistance for the potentiometer, which is 1~2 kΩ, 2 Watts.

Voltage Input – The voltage input circuit uses terminals [L] and [O]. Attach the signal cable’s shield wire only to terminal [L] on the inverter. Maintain the voltage within specifications (do not apply negative voltage).

Current Input – The current input circuit uses terminals [OI] and [L]. The current comes from a sourcing type transmitter; a sinking type will not work! This means the current must flow into terminal [OI], and terminal [L] is the return back to the transmitter. The input impedance from [OI] to

[L]is 100 Ohms. Attach the cable shield wire only to terminal [L] on the inverter.

AM H O OI L

1 to 2kΩ, 2W

 

AM

H

O

OI

L

 

0 to 9.6 VDC,

 

 

+ -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 to 10V nominal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AM

H

O

OI

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 to 19.6 mA DC,

4 to 20mA nominal

See I/O specs on page 21,22.

41

Image 43
Contents WJ200 Series Inverter Quick Reference Guide Page UL→ Cautions, Warnings and Instructions Marking RequirementsTerminal symbols and Screw size Fuse Sizes 5AT 123 45A-001 1005 Inverter Specification LabelModel-specific tables for 200V and 400V class inverters WJ200 Inverter SpecificationsWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating GFI Basic System DescriptionInverter + Motor Output Determining Wire and Fuse SizesAllowable current T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3 Wire the Inverter Input to a SupplyRB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Key and Indicator Legend Using the Front Panel KeypadPower LED Alarm LED Keypad Navigation Map Keys, Modes, and ParametersPRG LED Group a Group dGroup F SaveF001 Key GND Connecting to PLCs and Other DevicesMotor Example Wiring DiagramOutput Input Control Logic Signal SpecificationsPulse TrainSP, SN Wiring sample of control logic terminal sink logicSink/source logic of intelligent input terminals Wire size for control and relay terminalsRecommended ferrule Intelligent Inputs Intelligent Terminal ListingIntelligent Outputs Sink logic connection Using Intelligent Input TerminalsSource logic connection WJ200 Sinking Inputs, Internal SupplySourcing Inputs, Internal Supply Sourcing Inputs, External Supply Sinking Inputs, External SupplyOFF InsertingOption Terminal Code Symbol Function Name State Description Forward Run/Stop and Reverse Run/Stop CommandsMulti-Speed Select ~Binary Operation Required settingsFW,RV Two Stage Acceleration and Deceleration2CH Unattended Start Protection Option Terminal Function Name State Description Code SymbolUSP Reset Inverter Option Terminal Function Name Using Intelligent Output TerminalsRun Signal Code SymbolSettings Frequency Arrival SignalsRequired FA3/FA5 FA2/FA4Stop Alarm SignalTrip During normal operation AM H O OI L Analog Input OperationAM H O OI Other Analog Input-related topics SN 7 6 5 4 3 2 1 L PLC P24 Pulse Train Input OperationAnalog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D009 D006D007 D008D060 D029D030 D050Main Profile Parameters Standard Functions A021 ~ A035 A015A220 A241A044 A242A043 A243A261 A058A059 A061A075 A072A073 A074A293 A092A292 A093A142 A131A132 A141A162 A156A157 A161Fine Tuning Functions B213 B012B212 B013B028 B025B026 B027B040 B037B038 B039B063 B060B061 B062B090 B087B088 B089B101 B096B097 B100B150 B133B134 B145Intelligent Terminal Functions C032 C028C030 C031C054 C047C052 C053C081 C076C077 C078C105 C102C103 C104C150 C147C148 C149DWN AnlgFWD, REV PidcSF4 SF1SF2 SF3255 Run Signal When the inverter is in Run Mode LOG2 LOG1LOG3 MO3 C039MO1 MO2Motor Constants Functions PM Motor Constants Functions H117 H112H113 H116Expansion Card Functions P046 P041P044 P045P077 P072P073 P075Trip History and Inverter Status Monitoring Trip Events, History, & ConditionsError Name Causes Code Error CodesE37 Error Name Descriptions Code Restoring Factory Default SettingsOther indication Important notes CE-EMC Installation GuidelinesPage Page Metal plate earth Installation for WJ200 series example of SF modelsHitachi EMC Recommendations How it works Functional Safety Certification in ProgressIntroduction Stop Category defined in EN60204-1Installation Wiring example OFF G9SX GS9ANE1A