Hitachi hitachi series inverter B025, B026, B027, B028, B029, B030, B031, B033, B034, B035, B036

Page 62

 

 

 

 

 

 

 

Run

 

 

 

 

 

 

Func.

Name

 

 

Description

 

 

Mode

 

 

Initialdata

 

 

Units

Code

 

 

 

 

 

 

Edit

 

 

 

 

 

 

b025

Overload restriction level 2

 

 

Sets the level of overload restriction,

 

 

 

 

 

Rated

 

 

 

 

 

 

 

between 20% and 200% of the rated

 

 

 

 

 

current

 

 

 

 

 

 

 

current of the inverter, setting

 

 

 

 

 

x 1.5

 

 

 

 

 

 

 

resolution is 1% of rated current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b026

Deceleration rate 2 at overload

 

 

Sets the deceleration rate when

 

 

 

 

 

1.0

 

 

sec.

 

restriction

 

 

inverter detects overload, range is

 

 

 

 

 

 

 

 

 

 

 

 

 

0.1 to 3000.0, resolution 0.1

 

 

 

 

 

 

 

 

 

b027

OC suppression selection

 

 

Two option codes:

 

 

 

 

 

01

 

 

 

 

 

 

00Disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

01Enabled

 

 

 

 

 

 

 

 

 

B028

Current level of active freq.

 

 

Sets the current level of active freq.

 

 

 

 

 

Rated

 

 

A

 

matching

 

 

matching restart, range is

 

 

 

 

 

current

 

 

 

 

 

 

 

0.1*inverter rated current to

 

 

 

 

 

 

 

 

 

 

 

 

 

2.0*inverter rated current, resolution

 

 

 

 

 

 

 

 

 

 

 

 

0.1

 

 

 

 

 

 

 

 

 

B029

Deceleration rate of active

 

 

Sets the deceleration rate when

 

 

 

 

 

0.5

 

 

sec.

 

freq. matching

 

 

active freq. matching restart, range

 

 

 

 

 

 

 

 

 

 

 

 

 

is 0.1 to 3000.0, resolution 0.1

 

 

 

 

 

 

 

 

 

B030

Start freq. of active freq.

 

 

Three option codes:

 

 

 

 

 

00

 

 

 

matching

 

 

00

 

 

 

 

 

 

 

 

 

 

 

 

 

freq at previous shutoff

 

 

 

 

 

 

 

 

 

 

 

 

 

01start from max. Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

02start from set frequency

 

 

 

 

 

 

 

 

 

B031

Software lock mode selection

 

 

Prevents parameter changes, in five

 

 

 

 

 

01

 

 

 

 

 

 

options, option codes:

 

 

 

 

 

 

 

 

 

 

 

 

 

00all parameters except B031 are

 

 

 

 

 

 

 

 

 

 

 

 

 

locked when [SFT] terminal is

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

01all parameters except B031 and

 

 

 

 

 

 

 

 

 

 

 

 

 

output frequency F001 are

 

 

 

 

 

 

 

 

 

 

 

 

 

locked when [SFT] terminal is

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

02all parameters except B031 are

 

 

 

 

 

 

 

 

 

 

 

 

 

locked

 

 

 

 

 

 

 

 

 

 

 

 

 

03all parameters except B031 and

 

 

 

 

 

 

 

 

 

 

 

 

 

output frequency F001 are

 

 

 

 

 

 

 

 

 

 

 

 

 

locked

 

 

 

 

 

 

 

 

 

 

 

 

 

10High level access including

 

 

 

 

 

 

 

 

 

 

 

 

 

B031

 

 

 

 

 

 

 

 

 

 

 

 

 

See appendix C for the accessible

 

 

 

 

 

 

 

 

 

 

 

 

 

parameters in this mode.

 

 

 

 

 

 

 

 

 

B033

Motor cable length parameter

 

Set range is 5 to 20.

 

 

 

 

 

10.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b034

Run/power ON warning time

 

Range is,

 

 

 

 

 

0.

 

 

Hrs.

 

 

 

 

0.:Warning disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

1. to 9999.:

 

 

 

 

 

 

 

 

 

 

 

 

 

10~99,990 hrs (unit: 10)

 

 

 

 

 

 

 

 

 

 

 

 

 

1000 to 6553:

 

 

 

 

 

 

 

 

 

 

 

 

 

100,000~655,350 hrs (unit: 100)

 

 

 

 

 

 

 

 

 

B035

Rotation direction restriction

 

Three option codes:

 

 

 

 

 

00

 

 

 

 

 

 

00No restriction

 

 

 

 

 

 

 

 

 

 

 

 

 

01Reverse rotation is restricted

 

 

 

 

 

 

 

 

 

 

 

 

 

02Forward rotation is restricted

 

 

 

 

 

 

 

 

 

b036

Reduced voltage start

 

 

Set range, 0 (disabling the function),

 

 

 

 

 

2

 

 

selection

 

 

1 (approx. 6ms) to 255 (approx.

 

 

 

 

 

 

 

 

 

 

 

 

1.5s)

 

 

 

 

 

 

 

 

 

60

Image 62
Contents WJ200 Series Inverter Quick Reference Guide Page Marking Requirements UL→ Cautions, Warnings and InstructionsTerminal symbols and Screw size Fuse Sizes Inverter Specification Label 5AT 123 45A-001 1005WJ200 Inverter Specifications Model-specific tables for 200V and 400V class invertersWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Inverter + Basic System DescriptionGFI Allowable current Determining Wire and Fuse SizesMotor Output Wire the Inverter Input to a Supply T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3RB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Power LED Alarm LED Using the Front Panel KeypadKey and Indicator Legend PRG LED Keys, Modes, and ParametersKeypad Navigation Map Save Group dGroup F Group aF001 Key Connecting to PLCs and Other Devices GNDExample Wiring Diagram MotorTrain Control Logic Signal SpecificationsPulse Output InputWiring sample of control logic terminal sink logic SP, SNWire size for control and relay terminals Sink/source logic of intelligent input terminalsRecommended ferrule Intelligent Terminal Listing Intelligent InputsIntelligent Outputs Source logic connection Using Intelligent Input TerminalsSink logic connection Sourcing Inputs, Internal Supply Sinking Inputs, Internal SupplyWJ200 Sinking Inputs, External Supply Sourcing Inputs, External SupplyInserting OFFForward Run/Stop and Reverse Run/Stop Commands Option Terminal Code Symbol Function Name State DescriptionRequired settings Multi-Speed Select ~Binary Operation2CH Two Stage Acceleration and DecelerationFW,RV USP Option Terminal Function Name State Description Code SymbolUnattended Start Protection Reset Inverter Code Symbol Using Intelligent Output TerminalsRun Signal Option Terminal Function NameRequired Frequency Arrival SignalsSettings FA2/FA4 FA3/FA5Trip Alarm SignalStop During normal operation AM H O OI Analog Input OperationAM H O OI L Other Analog Input-related topics Pulse Train Input Operation SN 7 6 5 4 3 2 1 L PLC P24Analog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D008 D006D007 D009D050 D029D030 D060Main Profile Parameters Standard Functions A241 A015A220 A021 ~ A035A243 A242A043 A044A061 A058A059 A261A074 A072A073 A075A093 A092A292 A293A141 A131A132 A142A161 A156A157 A162Fine Tuning Functions B013 B012B212 B213B027 B025B026 B028B039 B037B038 B040B062 B060B061 B063B089 B087B088 B090B100 B096B097 B101B145 B133B134 B150Intelligent Terminal Functions C031 C028C030 C032C053 C047C052 C054C078 C076C077 C081C104 C102C103 C105C149 C147C148 C150Pidc AnlgFWD, REV DWNSF3 SF1SF2 SF4255 Run Signal When the inverter is in Run Mode LOG3 LOG1LOG2 MO2 C039MO1 MO3Motor Constants Functions PM Motor Constants Functions H116 H112H113 H117Expansion Card Functions P045 P041P044 P046P075 P072P073 P077Monitoring Trip Events, History, & Conditions Trip History and Inverter StatusError Codes Error Name Causes CodeE37 Other indication Restoring Factory Default SettingsError Name Descriptions Code CE-EMC Installation Guidelines Important notesPage Page Installation for WJ200 series example of SF models Metal plate earthHitachi EMC Recommendations Stop Category defined in EN60204-1 Functional Safety Certification in ProgressIntroduction How it worksInstallation Wiring example OFF NE1A GS9AG9SX