Hitachi hitachi series inverter C076, C077, C078, C081, C082, C085, C091, C096, C098, C099, C100

Page 71

 

 

 

 

 

 

 

 

 

 

 

 

 

Run

 

 

 

 

 

 

 

 

 

 

Func.

 

 

Name

 

 

 

Description

 

 

 

 

Mode

 

 

 

Initialdata

 

 

 

Units

 

 

Code

 

 

 

 

 

 

 

 

 

Edit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C076

 

Communication error

 

 

 

Selects inverter response to

 

 

 

 

 

 

 

 

02

 

 

 

 

 

 

 

select

 

 

 

communications error.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Five options:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00Trip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Decelerate to a stop and trip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02Disable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03Free run stop (coasting)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04Decelerates to a stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C077

 

Communication error

 

 

 

Sets the communications watchdog

 

 

 

 

 

 

 

 

0.00

 

 

 

sec.

 

 

 

 

time-out

 

 

 

timer period.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range is 0.00 to 99.99 sec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0 = disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C078

 

Communication wait time

 

 

 

Time the inverter waits after

 

 

 

 

 

 

 

 

0.

 

 

msec.

 

 

 

 

 

 

 

 

receiving a message before it

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transmits.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range is 0. to 1000. ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C081

 

O input span calibration

 

 

 

Scale factor between the external

 

 

 

 

 

 

 

 

100.0

 

 

%

 

 

 

 

 

 

 

 

 

frequency command on terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L–O (voltage input) and the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

frequency output,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

range is 0.0 to 200%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C082

 

OI input span calibration

 

 

Scale factor between the external

 

 

 

 

 

 

 

 

100.0

 

 

%

 

 

 

 

 

 

 

 

 

frequency command on terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L–OI (voltage input) and the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

frequency output,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

range is 0.0 to 200%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C085

 

Thermistor input (PTC)

 

 

 

Scale factor of PTC input.

 

 

 

 

 

 

 

 

100.0

 

 

%

 

 

 

 

 

span calibration

 

 

 

Range is 0.0 to 200%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C091

 

Debug mode enable

 

 

 

Displays debug parameters.

 

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

Two option codes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00Disable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Enable <Do not set>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(for factory use)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C096

 

Communication selection

 

 

 

00Modbus-RTU

 

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

01EzCOM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02EzCOM<administrator>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C098

 

EzCOM start adr. of master

 

01-08

 

 

 

 

 

 

 

 

01

 

 

 

C099

 

EzCOM end adr. of master

 

01-08

 

 

 

 

 

 

 

 

01

 

 

 

C100

 

EzCOM starting trigger

 

 

 

00Input terminal

 

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

 

 

 

 

01Always

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C101

 

Up/Down memory mode

 

 

 

Controls speed setpoint for the

 

 

 

 

 

 

 

 

00

 

 

 

 

 

 

 

selection

 

 

 

inverter after power cycle.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Two option codes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00Clear last frequency (return to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

default frequency F001)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Keep last frequency adjusted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

by UP/DWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

69

Image 71
Contents WJ200 Series Inverter Quick Reference Guide Page UL→ Cautions, Warnings and Instructions Marking RequirementsTerminal symbols and Screw size Fuse Sizes 5AT 123 45A-001 1005 Inverter Specification LabelModel-specific tables for 200V and 400V class inverters WJ200 Inverter SpecificationsWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Inverter + Basic System DescriptionGFI Allowable current Determining Wire and Fuse SizesMotor Output T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3 Wire the Inverter Input to a SupplyRB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Power LED Alarm LED Using the Front Panel KeypadKey and Indicator Legend PRG LED Keys, Modes, and ParametersKeypad Navigation Map Group a Group dGroup F SaveF001 Key GND Connecting to PLCs and Other DevicesMotor Example Wiring DiagramOutput Input Control Logic Signal SpecificationsPulse TrainSP, SN Wiring sample of control logic terminal sink logicSink/source logic of intelligent input terminals Wire size for control and relay terminalsRecommended ferrule Intelligent Inputs Intelligent Terminal ListingIntelligent Outputs Source logic connection Using Intelligent Input TerminalsSink logic connection Sourcing Inputs, Internal Supply Sinking Inputs, Internal SupplyWJ200 Sourcing Inputs, External Supply Sinking Inputs, External SupplyOFF InsertingOption Terminal Code Symbol Function Name State Description Forward Run/Stop and Reverse Run/Stop CommandsMulti-Speed Select ~Binary Operation Required settings2CH Two Stage Acceleration and DecelerationFW,RV USP Option Terminal Function Name State Description Code SymbolUnattended Start Protection Reset Inverter Option Terminal Function Name Using Intelligent Output TerminalsRun Signal Code SymbolRequired Frequency Arrival SignalsSettings FA3/FA5 FA2/FA4Trip Alarm SignalStop During normal operation AM H O OI Analog Input OperationAM H O OI L Other Analog Input-related topics SN 7 6 5 4 3 2 1 L PLC P24 Pulse Train Input OperationAnalog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D009 D006D007 D008D060 D029D030 D050Main Profile Parameters Standard Functions A021 ~ A035 A015A220 A241A044 A242A043 A243A261 A058A059 A061A075 A072A073 A074A293 A092A292 A093A142 A131A132 A141A162 A156A157 A161Fine Tuning Functions B213 B012B212 B013B028 B025B026 B027B040 B037B038 B039B063 B060B061 B062B090 B087B088 B089B101 B096B097 B100B150 B133B134 B145 Intelligent Terminal Functions C032 C028C030 C031C054 C047C052 C053C081 C076C077 C078C105 C102C103 C104C150 C147C148 C149DWN AnlgFWD, REV PidcSF4 SF1SF2 SF3255 Run Signal When the inverter is in Run Mode LOG3 LOG1LOG2 MO3 C039MO1 MO2Motor Constants Functions PM Motor Constants Functions H117 H112H113 H116Expansion Card Functions P046 P041P044 P045P077 P072P073 P075Trip History and Inverter Status Monitoring Trip Events, History, & ConditionsError Name Causes Code Error CodesE37 Other indication Restoring Factory Default SettingsError Name Descriptions Code Important notes CE-EMC Installation GuidelinesPage Page Metal plate earth Installation for WJ200 series example of SF modelsHitachi EMC Recommendations How it works Functional Safety Certification in ProgressIntroduction Stop Category defined in EN60204-1Installation Wiring example OFF NE1A GS9AG9SX