Hitachi hitachi series inverter B012, B212, B013, B213, B015, B016, B017, B018, B019, B020, B021

Page 61

 

 

 

 

 

 

 

 

 

Run

 

 

 

 

 

 

 

 

Func.

 

Name

 

 

 

Description

 

 

Mode

 

 

Initialdata

 

 

 

Units

 

Code

 

 

 

 

 

 

 

 

Edit

 

 

 

 

 

 

 

 

B012

 

Level of electronic thermal

 

 

 

Set a level between 20% and 100%

 

 

 

 

 

Rated

 

 

 

A

 

B212

 

Level of electronic thermal,

 

 

 

for the rated inverter current.

 

 

 

 

 

current for

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

each

 

 

 

 

 

 

2nd motor

 

 

 

 

 

 

 

 

 

inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

model *1

 

 

 

 

 

B013

 

Electronic thermal

 

 

 

Select from three curves, option

 

 

 

 

 

01

 

 

 

 

 

 

characteristic

 

 

 

codes:

 

 

 

 

 

 

 

 

 

 

 

B213

 

Electronic thermal

 

 

 

00Reduced torque

 

 

 

 

 

01

 

 

 

 

 

 

characteristic, 2nd motor

 

 

 

01Constant torque

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02Free setting

 

 

 

 

 

 

 

 

 

 

 

b015

 

Free setting electronic thermal

 

 

 

Range is 0 to 400Hz

 

 

 

 

 

0.0

 

 

 

Hz

 

 

 

~freq.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b016

 

Free setting electronic thermal

 

 

 

Range is 0 to inverter rated current

 

 

 

 

 

0.00

 

 

 

Amps

 

 

 

~current1

 

 

 

Amps

 

 

 

 

 

 

 

 

 

 

 

b017

 

Free setting electronic thermal

 

 

 

Range is 0 to 400Hz

 

 

 

 

 

0.0

 

 

 

Hz

 

 

 

~freq.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b018

 

Free setting electronic thermal

 

 

 

Range is 0 to inverter rated current

 

 

 

 

 

0.00

 

 

 

Amps

 

 

 

~current2

 

 

 

Amps

 

 

 

 

 

 

 

 

 

 

 

b019

 

Free setting electronic thermal

 

 

 

Range is 0 to 400Hz

 

 

 

 

 

0.0

 

 

 

Hz

 

 

 

~freq.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b020

 

Free setting electronic thermal

 

 

 

Range is 0 to inverter rated current

 

 

 

 

 

0.00

 

 

 

Amps

 

 

 

~current3

 

 

 

Amps

 

 

 

 

 

 

 

 

 

 

 

B021

 

Overload restriction operation

 

 

 

Select the operation mode during

 

 

 

 

 

01

 

 

 

 

 

 

mode

 

 

 

overload conditions, four options,

 

 

 

 

 

 

 

 

 

 

 

B221

 

Overload restriction operation

 

 

 

option codes:

 

 

 

 

 

01

 

 

 

 

 

 

mode, 2nd motor

 

 

 

00Disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Enabled for acceleration and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

constant speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02Enabled for constant speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03Enabled for acceleration and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

constant speed, increase speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at regen.

 

 

 

 

 

 

 

 

 

 

 

B022

 

Overload restriction level

 

 

 

Sets the level of overload restriction,

 

 

 

 

 

Rated

 

 

 

Amps

 

 

 

 

 

 

 

between 20% and 200% of the rated

 

 

 

 

 

current

 

 

 

 

 

 

 

 

 

 

 

current of the inverter, setting

 

 

 

 

 

x 1.5

 

 

 

 

 

 

 

Overload restriction level,

 

 

 

resolution is 1% of rated current

 

 

 

 

 

 

 

 

 

 

B222

 

 

 

 

 

 

 

 

 

Rated

 

 

 

Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2nd motor

 

 

 

 

 

 

 

 

 

current

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x 1.5

 

 

 

 

 

B023

 

Deceleration rate at overload

 

 

 

Sets the deceleration rate when

 

 

 

 

 

1.0

 

 

 

sec.

 

 

 

restriction

 

 

 

inverter detects overload, range is

 

 

 

 

 

 

 

 

 

 

 

B223

 

Deceleration rate at overload

 

 

 

0.1 to 3000.0, resolution 0.1

 

 

 

 

 

1.0

 

 

 

sec.

 

 

 

restriction, 2nd motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b024

 

Overload restriction operation

 

 

 

Select the operation mode during

 

 

 

 

 

01

 

 

 

 

 

 

mode 2

 

 

 

overload conditions, four options,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

option codes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00Disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01Enabled for acceleration and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

constant speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02Enabled for constant speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03Enabled for acceleration and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

constant speed, increase speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at regen.

 

 

 

 

 

 

 

 

 

 

 

59

Image 61
Contents WJ200 Series Inverter Quick Reference Guide Page UL→ Cautions, Warnings and Instructions Marking RequirementsTerminal symbols and Screw size Fuse Sizes 5AT 123 45A-001 1005 Inverter Specification LabelModel-specific tables for 200V and 400V class inverters WJ200 Inverter SpecificationsWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating GFI Basic System DescriptionInverter + Motor Output Determining Wire and Fuse SizesAllowable current T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3 Wire the Inverter Input to a SupplyRB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Key and Indicator Legend Using the Front Panel KeypadPower LED Alarm LED Keypad Navigation Map Keys, Modes, and ParametersPRG LED Group F Group dSave Group aF001 Key GND Connecting to PLCs and Other DevicesMotor Example Wiring DiagramPulse Control Logic Signal SpecificationsTrain Output InputSP, SN Wiring sample of control logic terminal sink logicSink/source logic of intelligent input terminals Wire size for control and relay terminalsRecommended ferrule Intelligent Inputs Intelligent Terminal ListingIntelligent Outputs Sink logic connection Using Intelligent Input TerminalsSource logic connection WJ200 Sinking Inputs, Internal SupplySourcing Inputs, Internal Supply Sourcing Inputs, External Supply Sinking Inputs, External SupplyOFF InsertingOption Terminal Code Symbol Function Name State Description Forward Run/Stop and Reverse Run/Stop CommandsMulti-Speed Select ~Binary Operation Required settingsFW,RV Two Stage Acceleration and Deceleration2CH Unattended Start Protection Option Terminal Function Name State Description Code SymbolUSP Reset Inverter Run Signal Using Intelligent Output TerminalsCode Symbol Option Terminal Function NameSettings Frequency Arrival SignalsRequired FA3/FA5 FA2/FA4Stop Alarm SignalTrip During normal operation AM H O OI L Analog Input OperationAM H O OI Other Analog Input-related topics SN 7 6 5 4 3 2 1 L PLC P24 Pulse Train Input OperationAnalog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D007 D006D008 D009D030 D029D050 D060Main Profile Parameters Standard Functions A220 A015A241 A021 ~ A035A043 A242A243 A044A059 A058A061 A261A073 A072A074 A075A292 A092A093 A293A132 A131A141 A142A157 A156A161 A162Fine Tuning Functions B212 B012B013 B213B026 B025B027 B028B038 B037B039 B040B061 B060B062 B063B088 B087B089 B090B097 B096B100 B101B134 B133B145 B150Intelligent Terminal Functions C030 C028C031 C032C052 C047C053 C054C077 C076C078 C081C103 C102C104 C105C148 C147C149 C150FWD, REV AnlgPidc DWNSF2 SF1SF3 SF4255 Run Signal When the inverter is in Run Mode LOG2 LOG1LOG3 MO1 C039MO2 MO3Motor Constants Functions PM Motor Constants Functions H113 H112H116 H117Expansion Card Functions P044 P041P045 P046P073 P072P075 P077Trip History and Inverter Status Monitoring Trip Events, History, & ConditionsError Name Causes Code Error CodesE37 Error Name Descriptions Code Restoring Factory Default SettingsOther indication Important notes CE-EMC Installation GuidelinesPage Page Metal plate earth Installation for WJ200 series example of SF modelsHitachi EMC Recommendations Introduction Functional Safety Certification in ProgressStop Category defined in EN60204-1 How it worksInstallation Wiring example OFF G9SX GS9ANE1A