Hitachi hitachi series inverter Control Logic Signal Specifications, Pulse, Train, Output Input

Page 23

Control Logic Signal Specifications

The control logic connectors are located just behind the front housing cover. The relay contacts are just to the left of the logic connectors. Connector labeling is shown below.

RS485

Logic inputs

comm.

Relay contacts

AL2 AL1 AL0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SN

7

 

6

 

5

4

 

3

 

2

 

1

 

L

 

PLC

P24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Jumper wire

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP

 

EO

 

EA

H

 

O

 

OI

 

L

 

AM

CM2

 

12

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS485

Pulse

Pulse

 

Analog

 

Analog

 

Logic

comm.

Train

Train

 

input

 

 

output

 

output

 

 

 

 

output

input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P24

+24V for logic inputs

24VDC, 100mA. (do not short to terminal L)

PLC

Intelligent input common

To change to sink type, remove the jumper

 

 

wire between [PLC] and [L], and connect it

 

 

between [P24] and [PLC]. In this case,

 

 

connecting [L] to [1]~[7] makes each input

 

 

ON. Please remove the jumper wire when

 

 

using external power supply.

1

Discrete logic inputs

27VDC max. (use PLC or an external supply

2

(Terminal [3],[4],[5] and [7]

referenced to terminal L)

3/GS1

have dual function. See

 

4/GS2

following description and

 

5/PTC

related pages for the details.)

 

6

 

 

7/EB

 

 

GS1(3)

Safe stop input GS1

Functionality is based on ISO13849-1

GS2(4)

Safe stop input GS2

See appendix for the details.

PTC(5)

Motor thermistor input

Connect motor thermistor between PTC and

 

 

L terminal to detect the motor temperature.

 

 

Set 19 in C005.

EB(7)

Pulse train input B

2kHz max.

 

 

Common is [PLC]

EA

Pulse train input A

32kHz max.

 

 

Common is [L]

L (in upper row) *1

GND for logic inputs

Sum of input [1]~[7] currents (return)

11/EDM

Discrete logic outputs [11]

50mA max. ON state current,

 

(Terminal [11] has dual

27 VDC max. OFF state voltage

 

function. See following

Common is CM2

 

description and related pages

In case the EDM is selected, the functionality

 

for the details.)

is based on ISO13849-1

 

 

4VDC max. ON state voltage depression

12

Discrete logic outputs [12]

50mA max. ON state current,

 

 

27 VDC max. OFF state voltage

 

 

Common is CM2

CM2

GND for logic output

100 mA: [11], [12] current return

AM

Analog voltage output

0~10VDC 2mA maximum

EO

Pulse train output

10VDC 2mA maximum, 32kHz maximum

L (in bottom row) *2

GND for analog signals

Sum of [OI], [O], and [H] currents (return)

OI

Analog current input

4 to 19.6 mA range, 20 mA nominal,

 

 

input impedance 100 Ω

21

Image 23
Contents WJ200 Series Inverter Quick Reference Guide Page UL→ Cautions, Warnings and Instructions Marking RequirementsTerminal symbols and Screw size Fuse Sizes 5AT 123 45A-001 1005 Inverter Specification LabelModel-specific tables for 200V and 400V class inverters WJ200 Inverter SpecificationsWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Inverter + Basic System DescriptionGFI Allowable current Determining Wire and Fuse SizesMotor Output T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3 Wire the Inverter Input to a SupplyRB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Power LED Alarm LED Using the Front Panel KeypadKey and Indicator Legend PRG LED Keys, Modes, and ParametersKeypad Navigation Map Group a Group dGroup F SaveF001 Key GND Connecting to PLCs and Other DevicesMotor Example Wiring DiagramOutput Input Control Logic Signal SpecificationsPulse TrainSP, SN Wiring sample of control logic terminal sink logicSink/source logic of intelligent input terminals Wire size for control and relay terminalsRecommended ferrule Intelligent Inputs Intelligent Terminal ListingIntelligent Outputs Source logic connection Using Intelligent Input TerminalsSink logic connection Sourcing Inputs, Internal Supply Sinking Inputs, Internal SupplyWJ200 Sourcing Inputs, External Supply Sinking Inputs, External SupplyOFF InsertingOption Terminal Code Symbol Function Name State Description Forward Run/Stop and Reverse Run/Stop CommandsMulti-Speed Select ~Binary Operation Required settings2CH Two Stage Acceleration and DecelerationFW,RV USP Option Terminal Function Name State Description Code SymbolUnattended Start Protection Reset Inverter Option Terminal Function Name Using Intelligent Output TerminalsRun Signal Code SymbolRequired Frequency Arrival SignalsSettings FA3/FA5 FA2/FA4Trip Alarm SignalStop During normal operation AM H O OI Analog Input OperationAM H O OI L Other Analog Input-related topics SN 7 6 5 4 3 2 1 L PLC P24 Pulse Train Input OperationAnalog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D009 D006D007 D008D060 D029D030 D050Main Profile Parameters Standard Functions A021 ~ A035 A015A220 A241A044 A242A043 A243A261 A058A059 A061A075 A072A073 A074A293 A092A292 A093A142 A131A132 A141A162 A156A157 A161Fine Tuning Functions B213 B012B212 B013B028 B025B026 B027B040 B037B038 B039B063 B060B061 B062B090 B087B088 B089B101 B096B097 B100B150 B133B134 B145Intelligent Terminal Functions C032 C028C030 C031C054 C047C052 C053C081 C076C077 C078C105 C102C103 C104C150 C147C148 C149DWN AnlgFWD, REV PidcSF4 SF1SF2 SF3255 Run Signal When the inverter is in Run Mode LOG3 LOG1LOG2 MO3 C039MO1 MO2Motor Constants Functions PM Motor Constants Functions H117 H112H113 H116Expansion Card Functions P046 P041P044 P045P077 P072P073 P075Trip History and Inverter Status Monitoring Trip Events, History, & ConditionsError Name Causes Code Error CodesE37 Other indication Restoring Factory Default SettingsError Name Descriptions Code Important notes CE-EMC Installation GuidelinesPage Page Metal plate earth Installation for WJ200 series example of SF modelsHitachi EMC Recommendations How it works Functional Safety Certification in ProgressIntroduction Stop Category defined in EN60204-1Installation Wiring example OFF NE1A GS9AG9SX