Pulse Train Input Operation
The WJ200 inverter is capable of accepting pulse train input signals, that are used for frequency command, process variable (feedback) for PID control, and simple positioning. The dedicated terminal is called “EA” and “EB”. Terminal “EA” is a dedicated terminal, and the terminal “EB” is an intelligent terminal, that has to be changed by a parameter setting.
RS485 |
|
comm. | Logic input |
Relay contact
SN 7 6 5 4 3 2 1 L PLC P24
Jumper wire
AL2 AL1 AL0
| SP |
| EO | EA | H | O | OI | L | AM | CM2 | 12 | 11 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RS485 |
| Pulse | Pulse |
| Analog |
|
| Analog | Logic | |||||||
comm. | Train | Train | input |
|
| output |
| output | ||||||||
| output | input |
|
|
|
|
|
|
|
|
|
|
|
|
|
EA | Pulse train input A | For frequency command, 32kHz max. |
|
| Reference voltage: Common is [L] |
EB | Pulse train input B | 27Vdc max. |
(Input terminal 7) | (Set C007 to 85 ) | For frequency command, 2kHz max. |
|
| Reference voltage: Common is [PLC] |
(1) Frequency Command by pulse train input
When using this mode, you should set A001 to 06. In this case the frequency is detected by
(2) Using for process variable of PID control
You can use the pulse train input for process variable (feedback) of PID control. In this case you need to set A076 to 03. Only “EA” input terminal is to be used.
(3) Simple positioning by pulse train input
This is to use the pulse train input like an encoder signal. You can select three types of operation.