Hitachi hitachi series inverter SF1, SF2, SF3, SF4, SF5, SF6, SF7, Olr, Off Bok, MI1, MI2

Page 75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Option

 

 

Terminal

 

 

Function Name

 

 

 

Description

 

 

 

Code

 

 

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

29

 

 

UDC

 

Remote Control Data

 

ON

Clears the UP/DWN frequency memory by forcing it to

 

 

 

 

 

 

 

 

 

Clearing

 

 

equal the set frequency parameter F001. Setting C101

 

 

 

 

 

 

 

 

 

 

 

 

 

must be set=00 to enable this function to work

 

 

 

 

 

 

 

 

 

 

 

 

OFF

UP/DWN frequency memory is not changed

 

 

 

31

 

 

OPE

Operator Control

 

ON

Forces the source of the output frequency setting A001

 

 

 

 

 

 

 

 

 

 

 

 

 

and the source of the Run command A002 to be from

 

 

 

 

 

 

 

 

 

 

 

 

OFF

the digital operator

 

 

 

 

 

 

 

 

 

 

 

 

 

Source of output frequency set by A001 and source of

 

 

 

 

 

 

 

 

 

 

 

 

 

Run command set by A002 is used

 

 

 

32

 

 

SF1

Multi-speed Select,

 

ON

Bit encoded speed select, Bit 1, logical 1

 

 

 

 

 

 

 

 

 

Bit operation Bit 1

 

OFF

Bit encoded speed select, Bit 1, logical 0

 

 

 

33

 

 

SF2

Multi-speed Select,

 

ON

Bit encoded speed select, Bit 2, logical 1

 

 

 

 

 

 

 

 

 

Bit operation Bit 2

 

OFF

Bit encoded speed select, Bit 2, logical 0

 

 

 

34

 

 

SF3

Multi-speed Select,

 

ON

Bit encoded speed select, Bit 3, logical 1

 

 

 

 

 

 

 

 

 

Bit operation Bit 3

 

OFF

Bit encoded speed select, Bit 3, logical 0

 

 

 

35

 

 

SF4

Multi-speed Select,

 

ON

Bit encoded speed select, Bit 4, logical 1

 

 

 

 

 

 

 

 

 

Bit operation Bit 4

 

OFF

Bit encoded speed select, Bit 4, logical 0

 

 

 

36

 

 

SF5

Multi-speed Select,

 

ON

Bit encoded speed select, Bit 5, logical 1

 

 

 

 

 

 

 

 

 

Bit operation Bit 5

 

OFF

Bit encoded speed select, Bit 5, logical 0

 

 

 

37

 

 

SF6

Multi-speed Select,

 

ON

Bit encoded speed select, Bit 6, logical 1

 

 

 

 

 

 

 

 

 

Bit operation Bit 6

 

OFF

Bit encoded speed select, Bit 6, logical 0

 

 

 

38

 

 

SF7

Multi-speed Select,

 

ON

Bit encoded speed select, Bit 7, logical 1

 

 

 

 

 

 

 

 

 

Bit operation Bit 7

 

OFF

Bit encoded speed select, Bit 7, logical 0

 

 

 

39

 

 

OLR

 

Overload Restriction

 

ON

Perform overload restriction

 

 

 

 

 

 

 

 

 

Source Changeover

 

OFF

Normal operation

 

 

 

 

40

 

 

TL

 

Torque Limit Selection

 

ON

Setting of b040 is enabled

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Max. torque is limited with 200%

 

 

 

41

 

 

TRQ1

Torque limit switch 1

 

ON

Torque limit related parameters of Powering/regen, and

 

 

 

 

 

 

 

 

 

 

 

 

OFF

FW/RV modes are selected by the combinations of

 

 

 

42

 

 

TRQ2

Torque limit switch 2

 

ON

these inputs.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

44

 

 

BOK

Brake confirmation

 

ON

b124

) is valid

 

 

 

 

 

 

 

 

 

 

 

OFF

Brake wait time (

 

 

 

 

 

 

 

 

 

 

 

 

b124

) is not valid

 

 

 

 

 

 

 

 

 

 

 

 

 

Brake wait time (

 

 

 

46

 

 

LAC

 

LAD cancellation

 

ON

Set ramp times are ignored. Inverter output

 

 

 

 

 

 

 

 

 

 

 

 

 

immediately follows the freq. command.

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Accel. and/or decel. is according to the

 

 

 

 

 

 

 

 

 

 

 

 

 

set ramp time

 

 

 

 

47

 

 

PCLR

 

Pulse counter clear

 

ON

Clear the position deviation data

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Maintain the position deviation data

 

 

 

50

 

 

ADD

ADD frequency enable

 

ON

Adds the A145 (add frequency) value

 

 

 

 

 

 

 

 

 

 

 

 

OFF

to the output frequency

 

 

 

 

 

 

 

 

 

 

 

 

Does not add the A145 value to the

 

 

 

 

 

 

 

 

 

 

 

 

 

output frequency

 

 

 

 

51

 

 

F-TM

 

Force Terminal Mode

 

ON

Force inverter to use input terminals

 

 

 

 

 

 

 

 

 

 

 

 

OFF

for output frequency and Run command sources

 

 

 

 

 

 

 

 

 

 

 

 

Source of output frequency set by A001 and source of

 

 

 

 

 

 

 

 

 

 

 

 

 

Run command set by A002 is used

 

 

 

52

 

 

ATR

 

Enable torque

 

ON

Torque control command input is enabled

 

 

 

 

 

 

 

 

 

command input

 

OFF

Torque control command input is disabled

 

 

 

53

 

 

KHC

 

Clear watt-hour data

 

ON

Clear watt-hour data

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

No action

 

 

 

 

56

 

 

MI1

General purpose input

 

ON

General purpose input (1) is made ON under EzSQ

 

 

 

 

 

 

 

 

(1)

 

 

OFF

General purpose input (1) is made OFF under EzSQ

 

 

 

57

 

 

MI2

General purpose input

 

ON

General purpose input (2) is made ON under EzSQ

 

 

 

 

 

 

 

 

(2)

 

 

OFF

General purpose input (2) is made OFF under EzSQ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

73

Image 75
Contents WJ200 Series Inverter Quick Reference Guide Page UL→ Cautions, Warnings and Instructions Marking RequirementsTerminal symbols and Screw size Fuse Sizes 5AT 123 45A-001 1005 Inverter Specification LabelModel-specific tables for 200V and 400V class inverters WJ200 Inverter SpecificationsWJ200 Inverter Specifications, … WJ200 inverters, 400V models Derating Basic System Description GFIInverter + Determining Wire and Fuse Sizes Motor OutputAllowable current T1 V/T2 W/T3 L1 S/L2 T/L3 U/T1 V/T2 W/T3 Wire the Inverter Input to a SupplyRB PD/+1 P/+ Three-phase 200V 11kW Three-phase 400V 11, 15kW Using the Front Panel Keypad Key and Indicator LegendPower LED Alarm LED Keys, Modes, and Parameters Keypad Navigation MapPRG LED Group a Group dGroup F SaveF001 Key GND Connecting to PLCs and Other DevicesMotor Example Wiring DiagramOutput Input Control Logic Signal SpecificationsPulse TrainSP, SN Wiring sample of control logic terminal sink logicSink/source logic of intelligent input terminals Wire size for control and relay terminalsRecommended ferrule Intelligent Inputs Intelligent Terminal ListingIntelligent Outputs Using Intelligent Input Terminals Sink logic connectionSource logic connection Sinking Inputs, Internal Supply WJ200Sourcing Inputs, Internal Supply Sourcing Inputs, External Supply Sinking Inputs, External SupplyOFF InsertingOption Terminal Code Symbol Function Name State Description Forward Run/Stop and Reverse Run/Stop CommandsMulti-Speed Select ~Binary Operation Required settingsTwo Stage Acceleration and Deceleration FW,RV2CH Option Terminal Function Name State Description Code Symbol Unattended Start ProtectionUSP Reset Inverter Option Terminal Function Name Using Intelligent Output TerminalsRun Signal Code SymbolFrequency Arrival Signals SettingsRequired FA3/FA5 FA2/FA4Alarm Signal StopTrip During normal operation Analog Input Operation AM H O OI LAM H O OI Other Analog Input-related topics SN 7 6 5 4 3 2 1 L PLC P24 Pulse Train Input OperationAnalog Output Operation AM signal offset and gain are adjustable, as indicated below Monitoring functions D009 D006D007 D008D060 D029D030 D050Main Profile Parameters Standard Functions A021 ~ A035 A015A220 A241A044 A242A043 A243A261 A058A059 A061A075 A072A073 A074A293 A092A292 A093A142 A131A132 A141A162 A156A157 A161Fine Tuning Functions B213 B012B212 B013B028 B025B026 B027B040 B037B038 B039B063 B060B061 B062B090 B087B088 B089B101 B096B097 B100B150 B133B134 B145Intelligent Terminal Functions C032 C028C030 C031C054 C047C052 C053C081 C076C077 C078C105 C102C103 C104C150 C147C148 C149DWN AnlgFWD, REV PidcSF4 SF1SF2 SF3255 Run Signal When the inverter is in Run Mode LOG1 LOG2LOG3 MO3 C039MO1 MO2Motor Constants Functions PM Motor Constants Functions H117 H112H113 H116Expansion Card Functions P046 P041P044 P045P077 P072P073 P075Trip History and Inverter Status Monitoring Trip Events, History, & ConditionsError Name Causes Code Error CodesE37 Restoring Factory Default Settings Error Name Descriptions CodeOther indication Important notes CE-EMC Installation GuidelinesPage Page Metal plate earth Installation for WJ200 series example of SF modelsHitachi EMC Recommendations How it works Functional Safety Certification in ProgressIntroduction Stop Category defined in EN60204-1Installation Wiring example OFF GS9A G9SXNE1A